36
The user can press
UP
and
DOWN
cursor key to scroll through all the devices on the loop for
which the verify count is available. If there are no verified devices on the loop the following
message will be displayed.
If no verified devices with a non-zero counter are found on the specified loop(s), a message is
displayed to that effect.
Verification counters are cleared by the clear verification count command and at initial power-
up.
5. Maintenance report
The maintenance report displays all smoke sensors
on the
specified loop or loops detected as
dirty (
% alarm > 75
). The percent of alarm rises as the detector gets dirty. A trouble occurs
once the percentage reaches 75%. The report shows the device address, percentage dirty,
device type, and programmed message in the following format:
Enter the loop number of the desired device and press the
Enter
button.
The maintenance report is shown in the following format.
The user can press
UP
and
DOWN
cursor key to scroll through all the devices on the loop for
which the maintenance report is available. If there are no dirty devices on the loop the
following message will be displayed
6. A/P Report
The Advanced Protocol (AP) Report will display or list on a printer all local parameters of an AP
device currently connected on the SLC. This feature will list the internal register values of
current AP devices. Since parameter values and addresses are not disclosed to the user, this
tool is used to report information to Secutron technical support.
If the panel is connected to a printer the user will be prompted to select an output source:
If “Printer” is selected the user will be prompted to select the address range. “All” selects all
addresses from all configured loops and “Loop” selects addresses from one loop.
No verified devices
found
Loop Number
Loop :__
Maint Report
Percent dirty :012%
No dirty devices
found
- Report To -
1. Printer
2. Screen