35
•
Any system troubles.
•
Activation of any system common control or any command on the command menu.
The report format is similar to the alarm log report. Pressing the
INFO
key shows additional
information about the log.
3. Current level
The current levels report displays device information for each of all eligible devices on the
target loop (specified by user) or on all eligible devices on all loops if user specifies target loop
as '0'. Eligible devices will be those present in the configuration and also detected as present
on the real loops. Browsing through target address can be done using Up/Down keys. User
can indicate the device address to start with, but only if he indicated loop number as 1, 2, or 3.
Device information will consist of current analog values of the target and the percent of alarm if
device is an input. When the
Info
button is pressed the device type will be displayed together
with the alarm threshold if device is a smoke sensor.
Enter the loop number of the desired device and press the
Enter
button.
The display shows the loop number, device address, current level and the percentage alarm in
the following format:
The user can press
UP
and
DOWN
cursor key to scroll through all the analog devices on the
loop. If there are no analog devices on the loop the following message will be displayed.
4. Verify counts
The verification count report displays the number of times that the alarm verification cycle has
been initiated without causing an alarm for all verified device or circuits on the specified loop or
loops. If the count is zero, the device is not displayed.
Enter the loop number of the desired device and press the
Enter
button.
The report shows the loop#, device address and verify count in the following format:
Loop Number
Loop :__
Lp:1 Addr :001
Levl :0024 Alarm :000%
No analog devices
found
Loop Number
Loop :__
Lp:1 Addr :001
Verify count :000