44
5.10.10 Clear Verify Count
This operation is used to clear all the verification counts accumulated during the alarm
verification process. The user is prompted for confirmation as shown below:
After the confirmation the verification count is cleared and the information message is
displayed that the counts are cleared.
5.10.11 Ground Fault Test - Factory Use Only
Displays the system ground fault, positive and negative. When ground fault test is selected,
your passcode will be requested. An example of a ground fault test result is shown below.
5.10.12 Positive Alarm Sequence
If this feature is enabled the system allows for Positive Alarm Sequence alarm signals from
automatic fire detection devices. This selection is mutually exclusive with Two Stage
Operation, i.e. you can have one or the other and not both. Any devices deemed PAS will
activate the common alarm LED, the individual LED (if programmed), flash the Acknowledge
LED and sound the alarm buzzer at the panel. The LCD display will also declare the PAS
alarm. There will be no alarm signalling initially. All evacuation signal and off-premises
signalling will be activated if the Acknowledge button is not pressed within 15 seconds of the
PAS alarm and the RESET button is not pressed within 180 seconds from the acknowledge, or
if a second device goes into alarm.
Selecting this menu item will have one of three outcomes:
An error message when the feature is not configured:
“Enable Pos Alarm option first!”
An option to enable when the feature is available but has been bypassed:
"Pos Alarm disabled"
"Enable? Y/N"
An option to disable when the feature is available and enabled:
"Pos Alarm enabled"
"Disable? Y/N"
5.10.13 Exit
Exits to the main command menu.
Clear all verif
Counters ?Y/N
Verify
Counters cleared