72
Pre-Programmed Modes
11.10 Mode 10: Agent Release, Single Hazard, Not Cross-zoned,
Combined Release
11.10.1 Zone Configuration
•
Detection Zone -1: Alarm (Hazard Area1, not cross-zoned)
•
Detection Zone -2: Alarm (Hazard Area1, not cross-zoned)
•
Detection Zone -3: Alarm (Pressure Switch or Water-flow)
•
Detection Zone -4: Supervisory
•
Detection Zone -5: Abort Switch
•
Detection Zone -6: Manual Release
•
NAC -1: Signal, will be activated steady when there is any alarm zone active.
•
NAC -2: Signal, indicate the Hazard Area1 status.
•
RAC 1: Releasing Circuit
•
RAC -2: Releasing Circuit
11.10.2 Hazard Configuration
•
Default Release Timer Value: 60 seconds
•
Default Manual Release Delay: 0 seconds.
•
Default Abort Delay Type: Standard UL.
•
Soak Timer Value: 0 seconds (continuous)
11.10.3 NAC Configuration
•
Default Escalating NAC code of Hazard Area State:
• Hazard Idle: Off
• Hazard Alert: 20BPM
• Hazard Alarm: 60BPM
• Hazard Release: Steady
Detection Zones
Phantom Zones
Release Timers
Z1
Z2
Z3
Z4
Z5
Z6
Zp1
Zp2
RT1
Exp
RT2
Exp
Alm
Alm
WF
Supv
AB
MR
Z1+Z2
Z3+Z4
Out1
Signal
Steady
X
X
X
X
Out2
Signal
Escalating
X
(X)
X
X
Out3
Rel.
Releasing
X
X
Out4
Rel.
Releasing
X
X
RLS TMR 1 Started
X
RLS Tmr 1 Interrupted
X
RLS Tmr 1 Cancelled
X
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled