58
11.0
Pre-Programmed Modes
11.1
Mode 1: Agent Release, Single Hazard, Cross-zoned,
Combined Release
11.1.1 Zone Configuration
•
Detection Zone -1: Alarm (Hazard Area1, Cross-zoned)
•
Detection Zone -2: Alarm (Hazard Area1, Cross-zoned)
•
Detection Zone -3: Alarm (Pressure Switch or Water-flow)
•
Detection Zone -4: Supervisory (Non-latching by default)
•
Detection Zone -5: Abort Switch
•
Detection Zone -6: Manual Release Switch
•
NAC-1: Signal, will be on steady if there is any alarm zone or manual release switch
active.
•
NAC-2: Signal, indicates the cadence of hazard area 1 state or supervisory circuit
(optional).
•
RAC-1: Releasing Circuit (Hazard Area 1)
•
RAC-2: Releasing Circuit (Hazard Area 1)
11.1.2 Hazard Configuration
•
Default Release Timer Value: 60 seconds
•
Default Manual Release Delay: 0 seconds.
•
Default Abort Delay Type: Standard UL.
•
Default Soak Timer Value: 0 seconds
Detection Zones
Phantom Zones
Release Timers
Z1
Z2
Z3
Z4
Z5
Z6
Zp1
Zp2
RT1
Exp
RT2
Exp
Alm
Alm
WF
Sup
AB
MR
Z1+Z2
Z3+Z4
Out1
Signal
Steady
X
X
X
X
Out2
Signal
Escalating
X
(X)
X
X
Out3
Rel.
Releasing
X
X
Out4
Rel.
Releasing
X
X
RLS TMR 1 Started
X
RLS Tmr 1 Interrupted
X
RLS Tmr 1 Cancelled
X
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled