18
Cable and Jumper Connections for Main Board, Core Board and Adder Modules
Table 1 Connectors and Jumpers on the Main Fire Alarm Board
Table 2 Connectors and Jumpers on the Core Board
5.2
MR-2300-A Input Class-A Converter Adder Module
Figure 4
MR-2300-A Input Class-A Converter Adder Module
There are no jumpers or cables to set on this module, just wiring from the converter (wires are
fixed here) to the Main Fire Alarm Board.
Initiating circuits must be wired from the MR-2300-A module to the Main Fire Alarm board. For
example, Initiating circuit 1 positive (red) and negative (black) wires are connected to the
positive and negative terminals (respectively) of Initiating circuit 1 on the Main Fire Alarm
Board. From the MR-2300-A converter Initiating circuits are wired out to the devices from the
JW1
Remove this jumper if MR-2300-PR is connected.
P4
Cable from connector
P1
of the
MR-2306-R6 Relay Adder Module
connects here.
Otherwise not used.
JW2
Remove this jumper if an
MR-2306-R6 Relay Adder Module
is used.
JW4
Shorted if there is no external unit on RS485. This jumper works as ‘end of line’ jumper. If
one or more units are connected on RS485, only short on the last connected unit. JW4 on
all other units should be left open.
JW5
Normally open. To reset the password, place jumper here and power down the panel (both
AC power and batteries). Then power up the panel again, the password is restored to the
default after system startup. Once the system has reset,
REMOVE
the jumper from the pins
at JW5.
JW6
Normally open to BLOCK configuration via modem, PC with a UIMA converter module or a
CFG-300 Configuration Tool. Place jumper here to ALLOW any type of configuration.
JW4
Factory Use Only. Always Short.
JW5
Factory Use Only. Always Open.
BL
K
RE
D
BL
K
R
ED
BL
K
R
ED
BL
K
RE
D
BL
K
R
ED
BL
K
R
ED
- D
ET
1
O
U
T+
- D
ET2
O
UT+
- D
ET
3
O
UT
+
- D
ET
4
O
U
T+
- D
ET
5
O
U
T+
- D
ET6
OU
T+
- D
ET1
R
ET+
- D
ET2
R
ET+
- D
ET3
R
ET+
- D
ET4
R
ET+
- D
ET5
R
ET+
- D
ET6
R
ET+
mounting hole for
#6-32 screws
All these pins comes with
red and black wires which
are connected to the
detection circuit on the
main fire alarm board. Red
is positive and black is
negative
ICAC-306
mounting hole for
#6-32 screws
MR-2300-A