Faults
ASD 531, Technical description, T 140 416 en
99 / 105
10.3
Finding and rectifying faults
10.3.1
Fault states
With the aid of the event memory and the relevant event code display (can be called up from the SD memory card), it is possi-
ble to localize the error in the event of a fault. The table below lists the event codes for possible fault states and how to rectify
them. A list of all the event codes is provided in Sec. 8.5.4.3.
Notice
Multiple codes
: If there are multiple events for any given event group, the display readings are added together.
Example: Display
012
= event code
004
and
008
.
G10, smoke sensor events
Code Meaning:
Check:
Possible causes and remedy:
002
Smoke sensor dust
Check smoke sensor chamber, sampling
pipe and filter-box/filter unit for dust depos-
its
•
Clean interior of smoke sensor cham-
ber and insect protection screen
•
Check and clean sampling pipe and, if
necessary, filter-box / filter unit.
•
Replace smoke sensor
004
Smoke sensor dirt
Check smoke sensor chamber, sampling
pipe and filter-box/filter unit for dirt deposits
•
Clean interior of smoke sensor cham-
ber and insect protection screen
•
Check and clean sampling pipe and, if
necessary, filter-box / filter unit.
•
Replace smoke sensor
G11, smoke sensor faults, part 1
Code Meaning
Check:
Possible causes and remedy:
001
ASD <> smoke sensor communications
Ribbon cable connection
AMB, smoke sensor
•
Ribbon cable incorrectly attached or
defective
check, replace.
•
Smoke sensor defective
replace.
•
AMB defective
replace
002
Unknown smoke sensor type
(production fault)
Smoke sensor
•
Replace smoke sensor
008
Invalid parameters, smoke sensor
(production fault)
Smoke sensor
•
Replace smoke sensor
G12, smoke sensor, part 2
Code Meaning
Check:
Possible causes and remedy:
001
Smoke sensor measuring chamber
Smoke sensor
•
Smoke sensor defective
replace.
002
Temperature, smoke sensor
ASD ambient temperature
Smoke sensor
•
Adhere to ambient temperature specifi-
cations.
•
Smoke sensor defective
replace
004
Supply voltage, smoke sensor
Check ASD operating voltage
AMB, smoke sensor
•
Set operating voltage correctly
•
AMB defective
replace
•
Smoke sensor defective
replace
008
EEPROM access error, smoke sensor
Smoke sensor
•
Smoke sensor defective
replace
016
EEPROM invalid data, smoke sensor
Smoke sensor
•
Smoke sensor defective
replace
032
Manufacturing, smoke sensor
Smoke sensor
•
Smoke sensor defective
replace