ASD 531, Technical description, T 140 416 en
4.3.1.1
Values table for planning with “ASD PipeFlow”
After the calculation with “ASD PipeFlow”, the next more sensitivity value must be read from the table. Those on the AMB 31
must then be set accordingly.
“
Class
” rotary switch
Sensitivity range
1
2
3
“
Ho
le
s
”
se
n
si
ti
vi
ty r
o
tar
y sw
it
ch
1
10.000
1.202
0.144
2
8.683
1.044
0.125
3
7.539
0.906
0.109
4
6.546
0.787
0.095
5
5.684
0.683
0.082
6
4.935
0.593
0.071
7
4.285
0.515
0.062
8
3.721
0.447
0.054
9
3.231
0.388
0.047
A
2.805
0.337
0.041
B
2.436
0.293
0.035
C
2.115
0.254
0.031
D
1.836
0.221
0.027
E
1.594
0.192
0.023
F
1.384
0.166
0.020