8.5.4.2
Event groups
Event group
Purpose
G00
General events, part 1 (ASD On/Off, inactive, start initial reset, smoke sensor on/off from FACP)
G01
General events, part 2 (time, clear event memory)
G03
General events, part 3 (configuration change)
G04
General events, part 4 (reset events)
G10
Smoke sensor events (alarm, dust/dirt, pre-signals, alarm 2)
G11
Smoke sensor faults, part 1 (communication to ASD)
G12
Smoke sensor faults, part 2 (smoke sensor events)
G13
Isolate smoke sensor (On/Off, test results)
G30
Airflow monitoring sampling pipe (pipe blockage, pipe breakage,
LS-Ü
parameters, air flow sensor def./lacking)
G50
Fan faults (tacho signal, regulator, current consumption)
G60
Initial reset faults (various initial reset parameters, initial reset
time-out
, airflow too low)
G70
RIM faults
G71
XLM faults
G73
Memory card faults
G80
AMB faults (undervoltage, clock)
G81
Operating system faults
8.5.4.3
Event codes within event groups
G00, general events, part 1
001
Switch on ASD (supply voltage)
002
Initial reset carried out (ASD)
004
ASD switched off (inactive, via “External reset”)
008
ASD switched on (via “External reset”)
016
Smoke sensor switched off from FACP (SecuriFire – Integral)
064
Smoke sensor switched on from FACP (SecuriFire – Integral)
G01, general events, part 2
001
Date, time set
016
Event memory deleted
G03, general events, part 3, configuration changes
000
X01
015
W01
023
W09
031
W17
039
W25
047
W33
055
W41
001
X02
016
W02
024
W10
032
W18
040
W26
048
W34
056
W42
002
X03
017
W03
025
W11
033
W19
041
W27
049
W35
057
W43
003
A11
018
W04
026
W12
034
W20
042
W28
050
W36
058
W44
005
b11
007
b21
009
C11
011
C21
013
C31
G04, general events, part 4, reset results
001
Key
002
SecuriLine
008
External