SECO-LARM
ELECTROMAGNETIC LOCK
SECO-LARM U.S.A., Inc.
7
Wire Length
25ft. 50ft. 75ft. 100ft. 150ft. 200ft. 250ft. 300ft. 400ft. 500ft. 1000ft.
Wire Gauge @ 500mA 20 18 18
18
16
14
14
12
10
--
--
Wire Length
25ft. 50ft. 75ft. 100ft. 150ft. 200ft. 250ft. 300ft. 400ft. 500ft. 1000ft.
Wire Gauge @ 250mA 24 24 22
20
18
18
16
16
14
14
14
24VDC Minimum Wire Gauge:
Wiring Diagram:
Maximum Distance from Power Source to Electromagnetic Lock:
12VDC Minimum Wire Gauge:
Control
Device*
For a complete chart, please visit www.seco-larm.com
Optional
SECO-LARM
Electromagnetic Lock Accessories:
600-lb.
Models
1200-lb.
Models
E-941S-600/ZQ
E-941S-1K2/ZQ
E-941S-600/LQ
E-941S-1K2/LQ
E-941S-600/PQ
E-941S-1K2/PQ
E-941S-1K2/UQ
E-941S-600/UQ
“L” Brackets
Plate Spacers
“Z” Brackets
(includes 1 “L” Bracket)
Glass Door
“U” Brackets
E-941S-1K2/ZRQ
(Right-side “Z” Bracket
for E-941DA-1K2P)
E-941D-1K2/P
(for E-941DA-1K2P)
Additional
Models
E-941S-1K2/HQ
E-941S-600/HQ
Armature
Plate Holders
Description
*NOTE
: Connect switching devices like
push-to-exit switches between the
power source and the positive terminal
on the lock. Connecting switching
devices to the negative terminal may
cause a delay in unlocking.
Position a jumper over
the two middle pins for
24VDC operation
Position two jumpers
on all four pins for
12VDC operation
Voltage Selection Jumpers
Power Supply
Does not include armature plate
The Bond Status Sensor checks
to make sure the door is closed,
and the electromagnet is locked.
Bond Status Sensor:
Green Door is closed and locked
Red
Door not closed and/or locked
Off
Door in use / No power
600PQ and 1K2P models ONLY
LED Indicators:
(600PQ and 1K2P
models ONLY)
Note: Brackets and spacers are not available for E-941SA-300.
Note: E-941SA-300 is pre-wired.