16
Function 19
- Master Code
Default = Nil
Function 24
- Fault Relay
Default = 0
Function 25
– I/O Expander Board
61 62 only
Default = 0
If you want to restrict access to the SED-62/64
programming. Enter a 4 digit PIN number.
You will have to then enter *19pin# before you can
reprogram or gain access to the SED-62/64 once set
(by either Manual Mode or SMS Programming Mode)
Once the *19pin# is entered it will allow you into
the programming mode for 5 minutes.
Options:
Any 4 digit number
Example :
*
19
1234#
(Sets Master Code to 1234)
Sets the operation of the Fault Relay
Option 0 = relay operates in normal mode
Option 1 = Inverts relay to operate in fail safe mode
Option 2 = Disables relay as fault relay and relay is
controlled via SMS as relay 0.
(see Section 2.9 for SMS output control)
Options:
0 = Option 0
1 = Option 1
2 = Option 2
Example :
*
24
2#
(Relay controlled by SMS)
Enables the I/O expander board option. Only
enable this if an I/O expander board has been
plugged into the
SED 61/62 only
Once fitted this provided a additional
4 inputs and 4 outputs
Options:
0 = Disabled
1 = Enabled
Example :
*
25
1#
(I/O Expander Board Enabled)
Function 18
- SMS Zone Arming Confirmation
Default = 0
Enables confirmation SMS Message of arm / disarm
of Zones 1- 4 (Function 17 = 1) See Section 2.9 for
more details
Options:
0 = Disabled
1 = Enabled
Example :
*
18
1#
(SMS Confirmation Enabled)
Function 17
- Zone Input configuration
Default = 0
Sets the operation of the 4 Zone Inputs on the SED-62/64
Options:
0 = Option 0
1 = Option 1
2 = Option 2
Example :
*
17
1#
2.7
Option 0 = Zones 1-4 24 hour inputs
Option 1 = Zones 1-4 armed / disarmed via SMS
Option 2 = Zones 1-3 are 24 Hr but Zone 4 is a
control type and switches PSTN
over to GSM