                                                                                                 3                                                            rev. 3.0   13/06/2016 

 

- DS Input (NC) 
Photocell  operation  is  ignored  during  opening,  whereas  during 
closing they will reverse the direction of movement. 
 
To provide operation that meets EN 13849-1 Category 2, a test 
is  carried  out  on  the  photocells  prior  to  every  manoeuvre.  The 
control  unit  will  only  start  the  manoeuvre  if  the  test  is  passed: 
otherwise  the  control  unit  will  not  enable  any  movement,  and 
for  every  command  all  of  the  programming  leds  will  flash, 
signalling an alarm situation. 
 
Opening and Closing Limit Switch: 
The  control  unit  allows  the  Opening  and  Closing  Limit  Switch 
connection  (NC).  When  it  is  triggered  during  the  respective 
operating phases, movement stops immediately.  
Attention: Leave these inputs free if not used. 
 
Motor Power and Speed adjustment: 
The  electronic  control  unit  is  equipped  with  a  VR1  trimmer  to 
adjust  motor  Power  and  Speed,  fully  managed  by  the 
microprocessor. The adjustment can be made within a range of 
50% and 100% of the Maximum Power. 
Nevertheless,  every  movement  has  an  initial  surge,  powering 
the  motor  for  2  seconds  at  the  maximum  power  even  if  motor 
power adjustment is enabled. 
Attention:  You  will  need  to  repeat  the  teach-in  phase  if  you 
wish to adjust the VR1 trimmer as operation and deceleration 
times may be affected. 
 
Obstacle detection: 
The  electronic  control  unit  is  equipped  with  a  VR2  trimmer  to 
adjust  the  Counter  Power  required  to  detect  the  obstacle, fully 
managed by the microprocessor. 
The  adjustment  can  be  made  by  setting  a  time  interval 
between  a  minimum  of  0.1  seconds  and  a  maximum  of  3 
seconds.  
Note:  by  setting  the  VR2  trimmer  at  the  minimum,  the 
obstacle detection function is excluded.  
 
Attention: 
-  When  limit  switches  are  connected  to  the  control  unit,  the 
detection  of  an  obstacle  always  causes  the  motor  to  change 
direction  during  the  closing  phase,  and  also  during  the 
opening phase, for 2 seconds. 
- When no limit switches are connected to the control unit, the 
detection  of  an  obstacle  always  causes  the  motor  to  change 
direction  during  the  closing  phase  (except  for  the  last  5 
seconds  of  the  operation  when  it  performs  a  Stop)  and  to 
change  direction  for  2  seconds  during  the  opening 
phase(except  for  the  last  5  seconds  of  the operation when it 
performs a Stop). 
 
Motor Encoder: 
The control unit can have an Encoder integrated to the Motor. 
Encoders  can  be  used  by  the  control  unit  for  its  Obstacle 
Detection  function  to  guarantee  greater  precision  when 
operations are being carried out. 
 
Deceleration: 
The  motor  deceleration  function  is  used  on  the  gates  to  stop 
them  from  reaching  their  final  position  at  a  high  speed  in  the 
opening and closing phases.  
The  control  unit  allows  deceleration  to  be  programmed  for  the 
desired points (before the gates are completely open or closed) 
during Motor Timer programming (see Main menu). 
If  you  are  using  the  "Automatic  programming"  function  (see 
menu 2) it is also possible to include a deceleration phase (see 
Main menu). 
 
Operation with TIMER: 
The  control  unit  can  have  a  timer  set  up  instead  of  an  open-
close control button.  

Example: at 08:00 the timer closes the contact and the control 
unit  opens  the  gate.  At  18:00  the  timer  opens  the  contact  and 
the  control  unit  closes  the  gate.  During  the  interval  between 
08:00  and  18:00,  at  the  end  of  the  opening  phase,  the  control 
unit  disables  the  flashing  beacon,  automatic  closing  and  radio 
controls. 
 
Open Collector OUT 1-4 Output Operation: 
The  control  unit  has  4  open  collector  outputs  to  manage 
auxiliary functions:  
Out  1:  Out  1  will  be  active  in  flash  mode,  only  during  the 
Opening phase. 
Out  2:  Out  2  will  be  active  in  flash  mode,  only  during  the 
Closing phase. 
Out  3:  Out  3  will  be  steadily  active,  only  during  the  Pause 
phase. 
Out  4:  Out  4  will  be  steadily  active,  only  when  the  gate  is 
closed. 
 
Integration of the RTX 2278 - RTX2252 safety system. 
 
By  installing  module  RTX  2278  on  the  control  unit,  it  is 
automatically  possible  to  use,  via  radio,  the  functions  of  the 
safety system composed of transceiver RTX 2278 (Base) and a 
maximum of 2 RTX 2252 transceivers (Sensor 1 and Sensor 2).  
For  more  details  on  system  operation,  see  paragraphs    “RTX 
2278 Base” and “RTX 2252 Sensor”. 
Before starting any operation, the control unit carries out a test 
to make sure module RTX 2278 is working correctly; this fulfils 
EN 13849-1 Category 2 operation. 
Commands  from  Sensor  1  are  ignored  during  opening, 
whereas  during  closing  they  will  reverse  the  direction  of 
movement. 
Commands  from  Sensor  2  will  stop  movement  in  both  closing 
and opening phases. 
 
PROGRAMMING : 
 
The SEL key:this selects the type of function to be memorised, 
which is indicated by a flashing Led. 
Repeatedly  press  the  key  to  select  the  desired  function.    The 
selection  will  remain  active  for  10  seconds,  indicated  by  a 
flashing  Led.  If  no  other  operations  are  carried  out  during  this 
time, the control board will return to its previous state. 
The  SET  key:  this  programs  the  information  according  to  the 
type  of  function  previously  selected  with  the  SEL  button. 
IMPORTANT:  The  SET  key  function  can  also  be  replaced  by 
the radio-control, if previously programmed (CODE led on). 

 

MAIN MENU 

The  control  unit  is  provided  by  the  manufacturer  with  the 
possibility of selecting a number of important functions. 

---------------------- MAIN MENU ----------------- 

Led Reference Led off Led On 

1) CODE                     No code                          Code entered 
2) CODE PED.         No code                          Code entered 
3) IN.CMD.AP.          Disabled                           Enabled 
4) LAMP/CORT.      Flashing                  Courtesy Light  
5) PGM. AUT.      PGM Automatic=OFF         PGM Automatic=ON 
6) T. MOT.           Motor time 30 sec.          Programmed time 
7) T.MOT.PED.    Mot. Time Ped. 10 sec.     Programmed time 
8) T. PAUSA:       No auto close              With auto close 

 
1) CODE: 
 (Radio-control code) 
The  control  unit  allows  up  to  120  radio-controls  to  be 
memorised with different types of fixed or rolling codes. 
Programming. 
The transmission code is programmed in the following way: use 
the SEL key to move to the flashing CODE LED, at the same 
time send the pre-selected code from the radio-control you 
wish to use; when the CODE LED stays on steadily, 
programming is finished.  If all 120 available codes have been 
memorised, by repeating the programming operation, all 

Summary of Contents for LRX 2271

Page 1: ... up an isolating device inside the system It is necessary to install an omnipolar switch surge category III It must be positioned to provide protection from accidental closing pursuant to point 5 2 9 of EN 12453 6 For the power supply cables use flexible cables in an insulating sheath in harmonised polychloroprene H05RN F with a minimum conductor section of 1mm2 7 The various electrical components...

Page 2: ... Encoder Signal Input 3 GND Motor Encoder Power Supply OPERATING FEATURES Step by step operation By using either the radio control CODE led on or the low voltage buttons to activate the gate you obtain the following action the first impulse activates the opening mechanism until the motor time expires or the opening limit switch is reached the second impulse closes the gate If an impulse is sent be...

Page 3: ...e Main menu Operation with TIMER The control unit can have a timer set up instead of an open close control button Example at 08 00 the timer closes the contact and the control unit opens the gate At 18 00 the timer opens the contact and the control unit closes the gate During the interval between 08 00 and 18 00 at the end of the opening phase the control unit disables the flashing beacon automati...

Page 4: ...le If you do not want the control unit to decelerate when the opening and closing phase is finished press the SET key twice during programming instead of just once During programming it is possible to use the radio control key located on the control unit instead of the SET key only if previously memorised 7 T MOT PED Programming a pedestrian operating time of 4 minutes max The control unit is fact...

Page 5: ... 5 sec after the photocell disengages i e the gate closes 5 seconds after the user has passed through If you wish to enable the function proceed as follows check that Extended Menu 1 is enabled T MOT PED and T PAUSA Leds flash simultaneously use the SEL button to move to the flashing PGM AUT LED and then press the SET key the PGM AUT LED will light up steady and programming is complete Repeat the ...

Page 6: ...Menu 2 is enabled T MOT PED and T PAUSA LEDs start flashing simultaneously use the SEL button to move to the flashing T MOT LED then press the SET key at that point the T MOT LED will light up steady and programming is complete Accordingly the PUL input makes it possible to connect a button NO for the Opening phase only and the BL input to connect a button NO for the Closing phase only Repeat the ...

Page 7: ...tion paragraph It is then advisable to make sure that the preselected band is free not already in use by another device To carry out this check do the following using the SET key move to the PROGRAMMING MENU the Base scans the preselected frequency and if it is already occupied by the Base the MONITOR LED and PROGR MENU LEDs will flash alternately In this case proceed to select a different frequen...

Page 8: ... is dismantled from an installation it is advisable to take the batteries out so that the Sensor no longer continues unnecessary transmission NC or 8K2 Operating Mode Selection The RTX 2252 Device allows NC normally closed contact standard type or 8K2 resistance type sensitive edges to be connected Use Dip Switch SW2 No 1 to make the selection DIP 1 OFF NC input operation default DIP 1 ON 8K2 inpu...