4. inStallation
WarninG!
leave this mobile air-conditioner in an upright position for at least 2 hours before first use. Ensure that the air conditioner
remains in an upright position whilst it is being moved. Place the air-conditioner on a flat ground surface.
4.1.
Connector 25 and Window Sealing Board Assembly 28 are fitted to Exhaust Hose 26. Place 25 and 26 at each end of the hose and
screw clockwise onto the hose to connect.
exhaust hose retaining clamp assembly;
4.2.
select the exhaust hose retaining clamp.
4.3.
fit the exhaust hose to the circular aperture at the rear and secure with the retaining clamp. rotate the retaining clamp anticlockwise
and snap the retaining clamp closed to secure the Heat exhaust Hose.
4.4.
fit 27 window sealing board to the window as shown in fig 1 (vertical) or fig 2 (horizontal).
4.5.
Position the mobile air-conditioner, with the exhaust hose assembly attached, near to a window. Keep the mobile air conditioner at
least 50cm away from the walls or other objects. (As shown in fig 3)
4.6.
Snap the flat end of the exhaust hose connector into the elliptical hole of the window sealing board assembly (as shown in Fig 4 and
fig 5).
4.7.
to ensure adequate operation, ensure that the exhaust hose is not kinked, do not bend the exhaust hose any more than 45°.
important:
The exhaust hose is 280mm-1500mm long and this length is determined based on the specification of the air-conditioner (s). Do
not use hoses with other specifications. Do not replace with non-genuine components as this may affect the functions of the
air-conditioner. The flow of exhaust must be smooth. Obstructed exhaust may cause the air-conditioner to overheat.
fig.1
fig.2
fig.3
s
AC9001 | Issue 3 (L) 29/11/16
Original Language Version
© Jack sealey limited