Ad ices

Make sure all Safeties are turned ON

Problem Found

Possible Cause

Solutions

Gate opens, but will not close 
with transmitter or pause time 
different from OFF

a) Open control active                                                                                                                                                                                                                       
b) Pause not set                                                                                                                                                                                                                                                         
c) Close Entrapment Protecting Device active                                                                                                                                                                                      
d) Photocells contact is open                                                                                                                                                                                                                                                                                                                         
e) Fire-switch input active 

a) Check all Open inputs for an active input                                                                                                                                                                                                                   
b) Check pause settings                                                                                                                                                                                                                           
c) Check all Entrapment Protection Device inputs for an active 
sensor                                                                                                                                                                                                                              
d) Check photocells contact                                                                                                                                                                                                                                                         
e) Check fire-switch input

Gate doesn’t respect slow 
down points

a) ENCODER is not working properly if It's 
activated                                                                        
b) Mechanical clutch loose                                                             
c) Slow down space is too wide                                                                         
d) Potentiometer is not working properly if It's 
activated                                                                                                                                                                                                                                                                              
e) The recovery position parameters are too 
high or too low                                                                                                                                                                                                                                                         

a) Check menu for encoder parameters  "Encoder Par" shall be 
from a low value +/- 10 (gate completely closed) to "Encoder 
tot" (gate completely opened). If the movement of Ipar is not 
linear in the range (+/-10 - Encoder tot) probably the Encoder is 
defective                                                                                                                                                                                                                                                 
b) Tight mechanical clutch                                                                                                                                                                                                                           
c) Reduce slow down space                                                                                                                                                                                                                
d) Check menu for potentiometer parameters  "IPar" shall be 
from "I. CH."(gate completely closed)  to "I.AP." (gate 
completely opened). If the movement of Ipar is not linear in the 
range (I.AP. - I.CH.) probably the potentiometer is defective                                                                                                                                                                                                                                                                                                                                                                                                                  
e) Reduce or increase the recovery position parameters

Gate opens suddenly without 
start command

a) Frequency or other noise from main line                                                                                                                                        
b) Short circuit on the start contact

a) Wiring AC shall be separate from DC wire and pass through 
separate conduits. If there is a frequency noise it is possible to 
change frequency to another MHz like 868 for example or FM                                                                                                                                      
b) Check all start contacts

Gate doesn’t close in automatic 
logic during pause even if a 
loop/photo is set as start

a) START IN PAUSE is not in ON                                                          
b) The photo/loop input is not set as "Delay 
pause time"

a) Put in ON the menu of START IN PAUSE                                                                                                           
b) Set in the photo/loop menu "Delay pause time"

Gate doesn't have power to 
close or reach limit switch

a) Slow down not possible for that site due to 
heavy gate or inclination or not new 
installation

a) Put Slow Down in OFF

Obstruction in gates path does 
not cause gate to stop and 
reverse 

a) Force adjustment needed 

a) Refer to the Adjustment section to conduct the obstruction 
test and perform the proper force adjustment that is needed 
(sensitivity - torque)

Photoelectric sensor does not 
stop or reverse gate

a) Incorrect photoelectric sensor wiring                                          
b) Defective photoelectric sensor                                                           
c) Photoelectric sensors installed too far apart 

a) Check photoelectric sensor wiring. Retest that obstructing 
photoelectric sensor causes moving gate to stop, and may 
reverse direction                                                                                                                                                              
b) Replace defective photoelectric sensor. Retest that 
obstructing photoelectric sensor causes moving gate to stop, 
and may reverse direction                                                                                                                                                                                              
c) Move the photoelectric sensors closer together or use edge 
sensors instead

Edge Sensor does not stop or 
reverse gate

a) Incorrect edge sensor wiring                                                                                                   
b) Defective edge sensor 

a) Check edge sensor wiring. Retest that activating edge sensor 
causes moving gate to stop and reverse direction                                                                                                                                                                                                                                                                                                                                        
b) Replace defective edge sensor. Retest that activating edge 
sensor causes moving gate to stop and reverse direction 

Alarm sounds for 5 minutes or 
alarm sounds with a command   

a) Double entrapment occurred (two 
obstructions within a single activation)

a) Check for cause of entrapment (obstruction) detection and 
correct. Press the reset button to shut off alarm and reset the 
operator. 

Shadow loop does not keep 
gate at the open limit

a) Vehicle detector setup incorrectly                                                                                       
b) Defective vehicle loop detector                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       
c) Wrong settings

a) Review Shadow loop detector settings. Adjust settings as 
needed                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                          
b) Replace defective Shadow loop detector                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       
c) Check the photo2 menu is set on shadow loop

Accessories connected to the 
accessory power not working 
correctly, turning off or 
resetting

a) Accessory power protector active                                                                        
b) Defective control board                

a) Disconnect all accessory powered devices and measure 
accessory power voltage (should be 23-30 Vdc). If voltage is 
correct, connect accessories one at a time, measuring accessory 
voltage after every new connection                                                                                                              
b) Replace defective control board 

...NE

taliano

ENGLIS

International registered trademark n. 804888

63

Summary of Contents for USER 2 24V DG R1B ALL-IN

Page 1: ...CT C C T T T M D C MM D T TT T C T CT C D T T International registered trademark n 804888 SEA S p A ona Ind striale Sant Atto 4 2 eramo I AL elephone 1 41 a 1 44 seateam com seacom seateam com taliano I ALIAN taliano ENGLIS taliano RAN AIS taliano ES A L ...

Page 2: ...ions alarmes Componentes Conexiones umpers Conexiones en CN1 tart tart Peatonal to Foto lulas y imer m ara anda de se uridad Foto lulas u er Es ira de se uridad Cerradura ma n ti a Re e tor externo at h o enin losin Conexiones en CN2 Final de arrera Cerradura el tri a Conexiones en CN3 Conexi n motores Conexiones en CN5 Conexi n s it hin atterias E SUN E SUN Q Conexiones externas nidad de esti n E...

Page 3: ...r 1 ER 24 power suppl connector R G Programming connector R1 Rectifier umper RL1 RL2 Rela motor 2 RL RL4 Rela motor 1 LL 1 COMPONENTS E NI AL EA URES o er s ppl 24 30 mA A sorption in stand 20 C 50 C En ironment temperat re E ternal o 305 x 225 x 125 mm IP55 RE EIVER R 156 mm 100 mm N2 ER N U NA R G RL1 RL2 RL RL4 M 1 M 2 M M 4 R1 DIS LA D N 1 12 11 1 4 2 1 N1 14 1 1 1 1 1 2 2 24 2 2 N S LL E 1 ta...

Page 4: ...tp t it is possi le to connect a ma im m load of 2 mA R GRAMMING U NS UP DOWN OK N S R RE EIVER NA POWER 24V ER SU L E ERNAL M DULE NNE R E LL LL SEA L UD NNE R taliano ENGLIS International registered trademark n 804888 Partial opening Start Photocell 2 Common Safety Edge Common Common Photocell 1 Start Stop Antenna Flashing lamp AUX 24V 250 mA max 24VL 600 mA max Accessories Lamp ARNING he contro...

Page 5: ...ELL1AND ELL2 ma m clamp C M clamp C M clamp otocell clamp otocell clamp Note 1 To perform the self test connect the T positive to the clamp 10 AU and activate the Phototest function on men 4 From the ES menu it is possible to activate the self test also on a single photocell choosing from the menu options Note 2 The default settings are ELL1 closing ELL2 opening for further functions and managemen...

Page 6: ...double the edge contact will be controlled b a specific resistance value which detects an possible short circuit of the device If the device is unbalanced a specific alarm will appear on the displa Note 2 the safet edge functions can also be managed through the OLLY3 Lamp FL Safety Edge EXAMPLE OF CONNECTION LAMP AND SECURITY EDGE 24VL 600 mA max Accessories Lamp N1 1 12 11 1 EXAMPLE OF TWO 10K PH...

Page 7: ...Type NO NC COM EXAMPLE OF MAGNETIC LOCK WITH RELAY CODE 23105340 CONNECTION 4 12 MAGNE I L n clamps 1 and 11 TT T set men on T efore connectin t e Ma ock It is possible to connect a magnetic loc Mag oc through the Relay card code 23105340 or old model code 540202 5 to the control unit and to the e ternal power supply 12V 24V DC power supply in case of 12V 24V loc or to 230V power supply in case of...

Page 8: ...ate the Latch function press again the button used for its activation LA ENING opens and eeps the automa tion open If active no other t pe of Start command is accepted until the function is deactivated LA L SING closes and eeps the automa tion closed If active no other t pe of Start command is accepted until the function is deactivated ote The atch function can also be enabled on the second channe...

Page 9: ...to choose hether to or ith the openin limit s itch onl or ith the closin one onl or ith oth N C 5 CONNECTIONS ON CN2 14 1 1 1 1 1 2 N2 1 14 1 1 1 1 1 1 OPENING LIMIT SWITCH MOTOR 1 CLOSING LIMIT SWITCH MOTOR 1 OPENING LIMIT SWITCH MOTOR 2 CLOSING LIMIT SWITCH MOTOR 2 N C N C N C 2 ELE RI L n clamps 1 and 2 An Electric Loc 12 15 max can be connected Through men L IME it is possible to ad ust the el...

Page 10: ...nnection output M EN L SE M L SE EN Caution for the connection to the power grid refer to the regulations in force M1 M2 G N 11 V o 2 V se A dela ed on 2 V po er s ppl se A dela ed on 11 V po er s ppl o er S ppl Inp t Power suppl connection input ASE N NEU RAL G GR UND taliano ENGLIS International registered trademark n 804888 N E It is recommended to se a 10A differential s itch to protect the po...

Page 11: ... 12V S N GND E SUN UNI 2 1 11 charge 200mA charge 360mA charge 800mA GND PSOL 28V GND N1 S A A A ERIES 12V 12V GND N S charge 200mA charge 360mA charge 800mA E SUN UNI 2 1 11 4 It is possible to power the control unit using t o 12V atteries connected in series 24V 1 2Ah min connected in turn to the batter charger management unit and this latter connected to the solar panel l ays se t e atteries c ...

Page 12: ...e to manage 4 additional limit switches to set the slowdown starting points T e openin and closin limit s itc es m st e connected to t e electronic control nit To manage the additional limit switches refer to 1 4 SELE LIMI S I or f rt er details on connections f nctions or specifications of t e nit refer to t e rele ant T C C T CT taliano ENGLIS International registered trademark n 804888 The SEM ...

Page 13: ...EMEN taliano ENGLIS International registered trademark n 804888 I SURGE R E R IR UI NNE I N 1 2 4 1 2 4 OUTPUT INPUT GROUND WIRE It is possible to connect the SURGE R E R device to protect up to 6 inputs 24 power suppl from overvoltages due for example to the lightning stri es Simpl connect the cable of the accessor to be protected to the IN U of the SUR E PROTECTOR circuit and then from the corre...

Page 14: ... switched on The control unit is also equipped with a special men that allows the setting of various parameters and the configuration of the accessories To access E S E IALMENU choose one of the following 2 procedures A E SAME IME R SE NDS UP DOWN S E IAL MENU LANGUAGE 1 SPEEDAP M1 17 LANGUAGE 1 SPEEDAP M1 17 UP SPECIAL MENU 16 OK 1 2 taliano ENGLIS International registered trademark n 804888 INPU...

Page 15: ...ycle CLOSE OPEN CLOSE OK SE N ES E S AR MMAND R UG Skip this step if a Tx has already been stored UP UP OK E ERA R S AR S U AND E VIE ILL AU MA I ALL RE URN N E MAIN MENU PRESS TO EXIT FROM BASIC MENUAND RETURN TO THE INPUT STATUS VIEW ON THE DISPLAY OK OK Skip these steps to work in semi automatic logic UP PRESS TO ACCESS THE SPECIAL MENU OK 1 S E IAL MENU N E All other parameters ha e sef l defa...

Page 16: ...lls to the 3 MOTOR menu Press O to select the 3 MOTORS menu and enter the menu Use UPor DO N to scroll through the options Select the model b pressing O and the displa returns to the 3 MOTORS menu Use the UPbutton to scroll to the 4 MOTORS NUMBER menu Press O Press UPto choose 1 1 motor SIN LE LEAF or 2 2 motors DOUBLE LEAF Press O to confirm and the displa returns to the 4 MOTORS NUMBER menu Use ...

Page 17: ... the AR IAL ENING S AR button is held pressed when released the gate stops To carr out the complete opening and or closing c cles it is necessar to hold the respective buttons constantl pressed 2 US U NS L GI One S AR opens one AR IAL ENING S AR closes Aclosing input will not be accepted during opening A S AR command reopens during closing movement while the AR IAL ENING S AR to close will be igno...

Page 18: ...d in the 112 PASS ORD Special Menu If the password is wrong the message will be displa ed To change the password it is necessar to unloc the control unit first then repeat the procedure to set a new password f o for ot t e pass ord contact t e tec nical assistance ill e al ate et er or not to pro ide t e proced re for t e control nit nlockin T Password CAN NOT be set using the O 3 programmer To co...

Page 19: ...U 1 1 A ESS E IN U S S A US MENU AND MANAGEMEN Access the input status menu and scroll forward or bac ward through and b scrolling through the inputs these are shown in their current state in ON or OFF example or ithin this management menu it is possible to enable or disable the inputs for the procedure see the table in the next paragraph 15 2 The LIMIT S ITCHES inputs and the batter status 0 0 ca...

Page 20: ...HOTO 1 OFF PHOTO 2 ON PHOTO 2 OFF BACK TO THE STARTING MENU BACK TO THE STARTING MENU BACK TO THE STARTING MENU BACK TO THE STARTING MENU UP UP UP UP UP UP LIMIT SWITCH OPENING 1 ON UP DISPLAYS THE BATTERY TENSION OK EXIT THE INPUT MANAGEMENT MENU THE FOLLOWING MENUS ONLY DISPLAY THE CURRENT INPUT STATUS IT IS NOT ALLOWED TO MAKE CHANGES LIMIT SWITCH CLOSING 1 ON LIMIT SWITCH OPENING 2 ON LIMIT SW...

Page 21: ... 2 of the available functions The STARTfunction mustAL AYS be assigned If the second function assigned will be modified later then all the radio transmitters will acquire this last function on the second channel ARNING The first stored radio transmitter will determine the coding of the following ones if the first radio transmitter is stored as ROLLIN CODE then all the following radio transmitters ...

Page 22: ... 1 1 REM E N R LS R GRAMMING A LE PROGRAMMING OF THE PARTIAL OPENING AS SECOND CHANNEL PROGRAMMING OF THE STOP AS SECOND CHANNEL PROGRAMMING OF THE EXIT COURTESY LIGHT AS SECOND CHANNEL WITH EXTERNAL MANAGEMENT UNIT PROGRAMMING OF THE LATCH OPENING FUNCTION AS SECOND CHANNEL PROGRAMMING OF THE LATCH CLOSING FUNCTION AS SECOND CHANNEL DELETE A SINGLE REMOTE CONTROL CLEAR THE WHOLE RECEIVER MEMORY P...

Page 23: ... to 2 Allows to set the number of motors to be managed 1 On It reverses the opening with the closing or viceversa Note both motors and limit swiches are reversed Off Off Automatic Automatic Open stop close stop open Step by step type 1 Open stop close open Step by step type 2 2 button Two buttons Safety Safety Dead man Dead man Off Disabled semi automatic logics 1 240 Setting from 1 second to 4 mi...

Page 24: ...ion in case of obstacle 70 32 ENCODER On ON Encoder enabled OFF Encoder disabled shows working times learnt Off 32 ENCODER Potentiometer Enables the reading of the potentiometer with LE card Off 51 I PAR M1 52 I AP M1 From the value learned to 100 pulses 53 I CH M1 From the value learned to 100 pulses 54 I PAR M2 55 I AP M2 From the value learned to 100 pulses 56 I CH M2 From the value learned to ...

Page 25: ...ill Start at middle of the total stroke 20 63 DECELERATION 0 50 Adjust the passage between normal speed and slowdown speed 5 64 ACCELERATION 0 100 Acceleration ramp Adjusts the motor start 100 70 OPENING POSITION RECOVERY 0 15 seconds Retrieves the inertia of the motor in opening after Stop or reversing 1s 71 CLOSING POSITION RECOVERY 0 15 seconds Retrieves the inertia of the motor in closing afte...

Page 26: ...f ON the partial input will be activated to work on the auxiliary board SEM2 traffic light management board Off 90 PARTIAL OPENING 20 100 Setting from 20 to 100 100 Start Pause in partial opening same as in total opening Off Disabled 1 240 Setting from 1second to 4 minutes Off On photo2 On partial entry SP MENU 92 TIMER Turn the selected input into an input to connect an external clock to Off 88 C...

Page 27: ...losing If occupied the photocell blocks the movement as long as it is busy when released the opening movement continues Stop If the photocell is occupied before the Start input the Start will be ignored If the photocell is occupied after the Start input the photocell will be ignored If the photocell is occupied during closing the gate will reopen Stop and close If the photocell is occupied during ...

Page 28: ...loop RP pause reloading If the shadow loop is temporarily released the pause time is reloaded before closing Stop and open If the photocell is activated during opening the gate stops and will continue in opening only when the photocell is released It is ignored during closing Normal Normal N C contact 8K2 Active edge protected by a 8K2 resistor 8K2 Double Allows to connect two 8K2 protected edges ...

Page 29: ...w Start input Closing Uses the Partial Opening N O input the Partial Opening is so disabled The gate closes and stay closed till a new Start input 119 DISPLAY WRITING SPEED From 30 to 100 See Note 2 below 80 120 BASIC MENU Note 1 After initialization the parameters motor type and limit switch type remain on the value chosen in the setup program Note 2 Display writing speed set on 30 keeps writing ...

Page 30: ... displa The table below shows what faults are advised and what to do in the event of a malfunction However it is possible to read the last 10 fault warnings b accessing the 1 DIAGN S I menu Note 1 If M M M C C C D is displayed the maintenance or the reset of the performed cycles number is necessary see note below Note 2 To exit the alarms displa press O If the warning signal does not disappear car...

Page 31: ...stacle Gate doesn t reach the complete Open Closed position a Wrong setting of the limit switches b Error on programming c Gate is stopped by an obstacle d Torque too low e Gate is too heavy for automatic slow down a Set limit switches b Repeat programming c Remove obstacle d Increase torque parameter e Set the slow down on OFF Gate opens but doesn t close a The contacts of the photocells are conn...

Page 32: ...le for that site due to heavy gate or inclination or not new installation a Put Slow Down in OFF Obstruction in gates path does not cause gate to stop and reverse a Force adjustment needed a Refer to the Adjustment section to conduct the obstruction test and perform the proper force adjustment that is needed sensitivity torque Photoelectric sensor does not stop or reverse gate a Incorrect photoele...

Page 33: ...dicall based on the number of maneuvers performed over time and based on the t pe of operator if a change in friction malfunctioning or non compliance with the previousl set times are noticed it o ld e ad isa le to repro ram t e learnin times on t e control nit Periodicall clean the optical s stems of the photocells RE LA EMEN S An request for spare parts must be sent to p Teramo T seateam com SA ...

Page 34: ...or 36 months from the date of manufacturing written on the operator LA INUM The mechanical components of the operators belonging to this line are guaranteed for 36 months from the date of manufacturing written on the operator The base warrant 36 months will be extended for further 24 months up to a total of 60 months when it is acquired the certificate of warrant which will be filled in and sent t...

Page 35: ...SEA S p A declines all liabilit as concerns the automated s stem s securit and efficienc if components used are not produced b SEAS p A 10 For maintenance strictl use original parts b SEA 11 Do not modif in an wa the components of the automated s stem 12 The installer shall suppl all information concerning s stem s manual functioning in case of emergenc and shall hand over to the user the warnings...

Page 36: ...r the highest qualit levels and for our complete satisfaction Than s for choosing SEA Cet article a t produit suivant des proc dures d usinage strictes et il a singulièrement t test afin de garantir les plus hauts niveaux de qualit pour votre satisfaction Nous vous remercions d avoir choisi SEA Este articulo ha sido producido siguiendo rigidos procedimientos de elaboracion ha sido probando singola...

Page 37: ...tiva 2006 42 CE is built to be integrated into a machine or to be assembled with other machinery to create a machine under the provisions of Directive 2006 42 CE è conforme ai requisiti essenziali di sicurezza relativi al prodotto entro il campo di applicabilità delle Direttive Comunitarie 2014 35 UE e 2014 30 UE is conforming to the essential safety requirements related to the product within the ...

Page 38: ...Notes ...

Page 39: ......

Page 40: ...SEA S p A ona ind striale 4 2 S A eramo I AL el 1 41 r a a 1 44 seateam com seacom seateam com International registered trademark n 804888 ...

Reviews: