SEA USA USER 2 - 24V Manual Download Page 5

GROUNDING

Good grounding and proper surge suppression are an integral part of proper installation for 
a gate operator system.   One or all of the following may require surge suppressors: high 
voltage power lines, low voltage power lines, telephone lines, data lines, low voltage control 
lines and loops.   How much surge suppression is required depends upon how susceptible 
the area is to lightning and power surges.   Regardless, good grounding is essential.   To 
realize maximum protection, proper grounding and proper surge suppression is absolutely 
necessary.

If the circuit breaker box is located close to the gate operator system, for example, in a 
guard house, then the ground from that circuit can be used to ground the gate operator 
system. Eliminate all 90° bends in ground wires and keep a minimum of three feet between 
the surge suppressor and the equipment being protected.

If the power source or circuit breaker box is not located close to the gate operator system an 
Isolated Ground Zone (IGZ) needs to be created.   An IGZ can also be created if the circuit 
breaker box is located close by the gate operator system. An IGZ is an imaginary circle 
drawn around the gate operator system.   The gate operator system not only includes the 
gate operators and control panel, but all of the accessories and devices associated with it at 
that controlled entry point.   This includes loop detectors, card readers, digital entries, 
telephone entries, any device that has a ground or requires a ground and ali of the surge 
suppressors. The ground bus is a common ground point calied a Single Point Ground 
(SPG).   It is used to bond all the equipment and device grounds in the IGZ together.   The 
SPG is very important because it helps eliminate different ground potentials that can be 
present on the equipment.   In such cases, equipment damage occurs even with surge 
suppressors.

Do not use or connect the ground wire coming from the circuit breaker box.   By using an 
Isolated Ground Zone, you are separating the gate operator system from the house or 
building ground. This eliminates ground potentials. It is recommended that the ground bus 
be located in a separate NEMA type enclosure. All grounds will be tied to this ground bus. 
Some points to remember:

Keep all ground wires as straight as possible.   Do not have any sharp 90° bends. Have a 
minimum of 3 feet of wire between the surge suppressor and the equipment being 
protected.

Equipment ground wire should be a minimum of 12 AWG.   The main ground wire from the 
bus bar to the ground rod shouid be an 8 or 6 AWG copper wire.   Ground rod should be a 
minimum of 10 feet in length, longer depending on local soil conditions.

For more information regarding good grounding practices check: National Electric Code 
art. 250; IEEE Emerald Book, standard 100; International Association of Electric 
Inspectors.

IM

P

O

R

T

A

N

T

 S

A

F

E

T

Y

 I

N

S

T

R

U

C

T

IO

N

S

SAVE THESE INSTRUCTIONS

READ AND FOLLOW ALL INSTRUCTIONS

USER 2 - 24V

International registered trademark n. 2.777.971

67410925

REV 02 - 06/2010

5

Summary of Contents for USER 2 - 24V

Page 1: ...SER 2 24V USER 2 HIDRO 23024015 16 17 18 19 20 21 ELECTRONIC CONTROL UNIT FOR SWING OPERATORS 24V REV 02 06 2010 67410925 SEA USA Inc 10850 N W 21st unit 160 DORAL MIAMI Florida FL 33172 Phone 1 305 594 1151 Fax 1 305 594 7325 Toll Free 800 689 4716 ...

Page 2: ...y charger card h ell P otoc M9 1 2 om o C m n M16 1 2 Co m n m o A t nn n e a 1 2 n C m o mo BUS M15 M12 1 2 o mmon C STOP M11 1 2 3 4 5 E G een ncoder 1 r om on C m m t w c i i s it h Op 1 L Limit itch Cl 1 sw n e h t E co r 1 W i e d 1 n o r 1 wn 2V E c d Bro e M14 1 2 3 4 5 mi w h p Li t s itc O 2 L i w t C im t s c 2 i h l n Whi E oder t c 2 e E ncoder 2 reen G om C on m 2 V e w En o r 2 r n 1...

Page 3: ...A BETA CONNECTIONS 11 SELFLEARNING WORKING TIMES 12 SETTINGS SELECTION 13 EXTERNAL RECEIVER CONNECTION AND RADIO TRANSMITTER LEARNING 14 FUNCTIONING LOGICS 15 BUS SYSTEM DESCRIPTION 15 PROGRAMMER JOLLY PARAMETERS ADJUSTMENT 16 CONNECTION OF BATTERIES 18 ALARMS AND MAINTENANCE DESCRIPTION 18 TROUBLE SHOOTING 19 AND GUARANTEE 20 21 SAFETY PRECAUTIONS SALES CONDITIONS International registered tradema...

Page 4: ...the travel retest the gate operator Failure to adjust properly the gate operator properly can increases the risk of severe injury or death 5 Use the manual release only when gate is not moving 6 KEEP GATES PROPERLY BALANCED AND MAINTAINED An improper balancing or maintenance increases the risk of severe injury or death Have a qualified service personal to make repairs to cables spring assemblies a...

Page 5: ...rs digital entries telephone entries any device that has a ground or requires a ground and ali of the surge suppressors The ground bus is a common ground point calied a Single Point Ground SPG It is used to bond all the equipment and device grounds in the IGZ together The SPG is very important because it helps eliminate different ground potentials that can be present on the equipment In such cases...

Page 6: ...9 Photocell connection M10 Pedestrian start M11 Encoder Limit switch M1 M12 Stop M13 Security edge M14 Encoder Limit switch M2 M15 BUS accessories connection M16 Antenna CMD programmer connector Jolly CMR Receiver module connection CALM 24V power supply connection CPO Programmer connector OPEN 67410925 6 M1 M4 M6 M8 M11 M14 M16 CALM M3 M5 M7 M9 M10 M12 M13 M15 LED3 LED6 LED8 LED9 LED7 LED14 LED18 ...

Page 7: ...ventual putting out of function of the product must be executed by qualified staff only For the security of people it is important to follow with attention all the advises and instructions in this manual Awrong installation or a wrong use of the product can cause sever damages to people TECHNICALSPECIFICATIONS Control unit power supply Absorption in stand by Max motor charge Max accessories charge...

Page 8: ...ags out of the reach of children Save these instructions for further information attaching them to the technical documents This product has been projected and built exclusively for the use described in this instruciton manual Uses not indicated in this manual could damage the product and be source of danger SEAdeclines all responsibility for improper or different use from the one for which it has ...

Page 9: ...ocell in opening if activated it causes the interruption of the movement as long as it is busy for then continuing the opening as soon as it is released Note If the photocell is not connected put a jumper between the clamps 1 and 2 of M9 24V 0V C Connection Com Common The photocell is also usable in connection with BUS photocells 1 2 1 2 M5 RX TX Com N C 1 2 1 2 M9 JOLLYOPTIONS FOTOCLOSE activatio...

Page 10: ...hite For the right function of the limit switches there must be a corrsipondence between the direction of movement of the motors and the respective occupied limit switches Com Common C Contact Electric lock exit An electric lock of 12V 15W max can be connected The electric lock activates at every opening cycle for about 1 5 s 1 2 M13 Flashing Lamp 24V 15W Warning lamp The warning lamp advises that...

Page 11: ...30V power supply 6 3A delayed fuse on 115V power supply Motor 2 Output for Motor 2 connection M OPEN CLOSED M CLOSED OPEN Motor 1 Output for Motor 1 connection M OPEN CLOSED M CLOSED OPEN Power input Input for the connection of the electric power P PHASE LIVE N NEUTRAL G GROUND NOTICE for the connection to the electric power see the law in force 67410925 11 USER 2 24V International registered trad...

Page 12: ...d to hold pressed the SET buttonuntil the motors start in closing The settings of DEFAULT are SEMIAUTOMATIC LOGIC DOUBLE LEAF ENCODER OFF MIDDLE SPEED LEAF DELAY 3 S PAUSE 2 S AVERAGE TORQUE SLOWDOWN SPEED 30 LEARNING SPEED 50 ACCELERATION 70 DECELARATION 30 LEAF STROKE OFF ANTI INTRUSION OFF SELFTEST OFF PEDESTRIAN 100 PHOTO OPENING OFF MAX CYCLES 100000 MOTOR TYPE FLIPPER IF YOU WANT TO RESTORE ...

Page 13: ...l the executed number of cycles Selecting LED 10 and LED 12 with alternate flashing with the MENU button you enter into the motor torque adjustment With LED 10 and LED 12 flashing alternatively keep pressed the button SET while selecting the desired torque observing the color of the LEDS 19 20 21 Led L19 green turned on torque Low Led L20 yellow turned on torque Middle Led L21 red turned on torque...

Page 14: ...ansmitter the led19 green will turn off to signal the memorisation of the data now it returns to flash for 5 seconds waiting for other codes 3 If it is desired to also associate a command to the pedestrian start press SET again the led 20 yellow will flash for signalling that it is waiting for a code to be associated to the pedestrian opening 4 Press the desired button of the radio transmitter LED...

Page 15: ... search of the peripheral BUS in case of BUS error press contemporarily the buttons and of the display or press the button until led 20 turns on At this point keep pressed SET as long as led 20 does not turn off and led 19 turns on Photocells alignment If photocells are connected on the BUS it is necessary to line up the same before programming To do the alignment it is necessary to start a self l...

Page 16: ...RO Learning on alignment off signalling of the execution of the learning 32 Cicli exec 0 2 number of executed cycles Mem free 0 100 percentage of available memory for the learning of remote controls Indicates the type of motor set Speed 30 100 adjusts the motors speed Sl speed 30 100 adjusts the slow down speed Lear Speed 30 100 adjusts the learning speed Photocell Tx1 OK NP peripheral reveal not ...

Page 17: ...N C on the limit switch that if freed forces the motors in closing Pre flashing on off activation of the pre flashing Autotest photo on off activates autotest photocell Max cycle 0 100000 indicates the number of cycles after which it is necessary to follow up the maintenance Photo in opening on off activation photocell in opening Leaf storke on off leaf stroke to release lock the lock It allows to...

Page 18: ...s therefore verify if such are the connections and or the correct working of the photocells of the Stop button and or of the safety edge 2 The failure with 6 flashes refers to a collision with an obstacle which has been revealed by the ammeter sensor therefore it is necessary either to repalce the motor or to verify the conditions of the connections 3 Periodically in relation to the number of mano...

Page 19: ... fuse on the control unit led 1 turned on a Re lock the motor b Remove obstacle a Pause time set to high B Control unit in semi autom logic a Adjust pause time B Adjust the automatic or security logic a Wrong setting of the limit switches b Error on programming c Gate is stopped by an obstacle d The fitting geometry is inadequate e Torque too low a Set limit switches b Repeat programming c Remove ...

Page 20: ...ng efforts SPARE PARTS To obtain spare parts contact Tel 1 305 594 1151 Fax 1 305 594 7325 Toll Free 800 689 4716 e mail sales sea usa com INTENDED USE The USER 2 24V electronic control unit has been designed to be solely used as control unit for the automation of sliding gates LIMIT OF GUARANTEE The USER 2 24V electronic control unit is guaranteed for a period of 24 months The guarantee period st...

Page 21: ...be refused Customers must contact SEAfor instructions WARRANTY for the original buyer only Hydraulic and oil bath motors 36 months warranty from the date of invoice on manufacturing assembling and workmanship defects Electro mechanic motors and electronic control systems 24 months warranty from the date of invoice on manufacturing assembling and workmanship defects Lepus and Full Tank Standard mod...

Page 22: ......

Page 23: ......

Page 24: ...International registered trademark n 2 777 971 SEA USA Inc 10850 N W 21st unit 160 DORAL MIAMI Florida FL 33172 Phone 1 305 594 1151 Fax 1 305 594 7325 Toll Free 800 689 4716 ...

Reviews: