6500105 Connect IP 4 Core Motor Controller
Inputs on Motor Controller
1.
Contact Close Input
a.
Contact Close Input for local control
b.
Requires 2 x Momentary contacts duration minimum 50 milliseconds
c.
Dedicated contact for Up & Down
d.
Stop command is close opposite travel contact or both Up & Down together
2.
DC Trigger Input
a.
Down command is sent when a DC Voltage of 3 Volts @ 1mA minimum is applied to
input
b.
Up command is sent when a DC Voltage of less than 1.0 Volts DC @ 1mA is applied
to input.
c.
Maximum cable length 75 meters approximately based 24 AWG gauge cable
3.
Infra-Red Input
a.
Supplied with 2 channel IR transmitter
b.
Supplied with IR receiver with 300mm and 1.2M input lead
c.
IR operates on Group 1 default – can be changed in set up
6500105 Connect IP 4 Core Motor Controller
All inputs on module 1 are accessed by removing right hand end cap of screen canister
Continued Over.../
1. CONTACT CLOSE INPUT
•
Contact Close Input for local control
•
Requires 2 x Momentary contacts duration minimum 50 milliseconds
•
Dedicated contact for Up & Down
•
Stop command is close opposite travel contact or both Up & Down together
2. DC TRIGGER INPUT
•
Down command is sent when a DC Voltage of 3 Volts @ 1mA minimum is applied to input, a
Up command is sent
•
Up command is sent when a DC Voltage of less than 1.0 Volts DC @ 1mA is applied to input,
a Down command is sent
•
Maximum cable length 75 meters approximately based 24 AWG gauge cable
INSTRUCTIONS -
INTERFIT
PROJECTOR LIFT – FVI and HTI Series