10.10
SEL-787 Relay
Instruction Manual
Date Code 20081022
Testing and Troubleshooting
Commissioning Tests
Figure 10.7
Delta Voltage Source Connections
Step 3. Using the front-panel
SET/SHOW
or the serial port
SHOW
command, record the CTR
n
(where n = VIWDG setting), PTR,
and PHROT setting values.
Step 4. Apply the current and voltage quantities shown in Column 1 of
Values are given for PHROT := ABC and PHROT := ACB.
Step 5. Use the front-panel
METER
or the serial port
MET
command to
verify the results.
SEL-787
E01
E02
E03
E04
Voltage
Test
Source
VA
VB
VC
VN
Table 10.6
Power Quantity Accuracy—Delta Voltages
a
Applied Currents and Voltages
Real Power
(kW)
Reactive Power
(kVAR)
Power Factor
(pf)
PHROT := ABC
IAW
n
= 2.5
∠
–26
IBW
n
= 2.5
∠
–146
ICW
n
= 2.5
∠
+94
Expected:
P = 0.4677 • CTR
n
• PTR
Expected:
Q = 0.2286 • CTR
n
• PTR
Expected
pf = 0.90 lag
VAB = 120
∠
+30
VBC = 120
∠
–90
Measured:
Measured:
Measured:
PHROT := ACB
IAW
n
= 2.5
∠−
26
IBW
n
= 2.5
∠
+94
ICW
n
= 2.5
∠−
146
Expected:
P = 0.4677 • CTR
n
• PTR
Expected:
Q = 0.2286 • CTR
n
• PTR
Expected:
pf = 0.90 lag
VAB = 120
∠−
30
VBC = 120
∠+
90
Measured:
Measured:
Measured:
a
n = VIWDG setting
Summary of Contents for SEL-787
Page 1: ...20081022 SEL 787 Transformer Protection Relay Instruction Manual PM787 01 NB ...
Page 6: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 78: ...This page intentionally left blank ...
Page 206: ...This page intentionally left blank ...
Page 280: ...This page intentionally left blank ...
Page 334: ...This page intentionally left blank ...
Page 376: ...This page intentionally left blank ...
Page 388: ...This page intentionally left blank ...
Page 474: ...This page intentionally left blank ...
Page 508: ...This page intentionally left blank ...