SEL-749M Relay
Protection and Logic Functions
Basic Motor Protection
Additional Thermal
Overload Settings
When the motor thermal capacity used exceeds the overload warning level
setting (TCAPU), the relay issues a warning (the Relay Word bit 49A asserts).
The early warning may allow you to correct the load problem before a thermal
trip occurs. Set TCAPU using the following criteria to avoid nuisance
overload warnings when running the motor at full load:
Equation 4.1
The motor tripping and starting functions include supervision to help prevent a
thermal trip on a normal start. The relay prevents motor starting until the
thermal element has enough available starting thermal capacity to allow a
motor start without tripping. The available thermal capacity required to start is
(100–TCSTART), where TCSTART is the start inhibit level setting. This
feature can be disabled by setting TCSTART equal to OFF.
Equation 4.2
2.50
14.40
28.80
43.20
72.00
144
216
432
648.0
Starting Model
Limits
c
3.00
10.00
20.00
30.00
50.00
100
150
300
450.0
4.00
5.63
11.25
16.88
28.13
56.25
84.38
169
253.1
5.00
3.60
7.20
10.80
18.00
36.00
54.00
108
162.0
6.00
2.50
5.00
7.50
12.50
25.00
37.50
75.00
112.5
7.00
1.84
3.67
5.51
9.18
18.37
27.55
55.10
82.65
8.00
1.41
2.81
4.22
7.03
14.06
21.09
42.19
63.28
9.00
1.11
2.22
3.33
5.56
11.11
16.67
33.33
50.00
10.0
0.90
1.80
2.70
4.50
9.00
13.50
27.00
40.50
11.0
0.74
1.49
2.23
3.72
7.44
11.16
22.31
33.47
12.0
0.63
1.25
1.88
3.13
6.25
9.38
18.75
28.13
14.0
0.63
1.25
1.88
3.13
6.25
9.38
18.75
28.13
a
(Trip time for Curve n) = (Trip time for Curve 45)*n/45 at same multiple of FLA.
b
Tripping times are for the stator initially at operating temperature (hot).
c
Tripping times are for the rotor initially at ambient temperature (cold).
Table 4.5
Thermal Limit Tripping Times in Seconds vs. Multiples of Full-Load Amps (Service Factor = 1.01)
a
(Sheet 2 of 2)
Multiples of
FLA
Curve 1
Curve 2
Curve 3
Curve 5
Curve 10
Curve 15
Curve 30
Curve 45
Remarks
Table 4.6
Overload Settings (Alarm, Start Inhibit, Cooling, and RTD Bias)
Setting Prompt
Setting Range
Setting Name := Factory Default
OL WARN LEVEL
Off, 50–99 %TCU
TCAPU := 85
START INH. LEVEL
Off, 1–99 %TCU
TCSTART := OFF
STOP COOL TIME
1–6000 min
COOLTIME := 84
OL RTD BIASING
Y, N
ETHMBIAS := N
NOTE:
The overload warning feature
is enabled only during normal running
mode after a successful motor start.
TCAPU
100
SF
2
---------
>
TCSTART
Start%TCU
≥
Summary of Contents for SEL-749M
Page 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 14: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 20: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 52: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 118: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 224: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 274: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 286: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 306: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 310: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 314: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...