4.6
SEL-749M Relay
Instruction Manual
Date Code 20080918
Protection and Logic Functions
Basic Motor Protection
Phase current transformers with 100:5 A rating are selected for the
application. The SEL-749M settings for the application are calculated
as shown below:
Current Transformer Ratio: CTR1 := 100/5 := 20 (see
Full Load Amps (FLA): FLA1 := 80 A primary (see
Service Factor: SF := 1.2
Locked Rotor Amps: LRA1 := 480.0/80.0 := 6.0 xFLA
Hot Locked Rotor Time: LRTHOT1 := 15.0 seconds
Run State Time Constant: RTC1 := Auto
The acceleration factor (TD1) setting reduces or extends the allowed
accelerating time under locked rotor conditions. You can always safely set this
value equal to 1.00.
If you know that the driven load will always accelerate in less than the rated
locked rotor time, you may wish to use a TD1 setting less than 1.00 to provide
a faster trip in locked rotor conditions. Do not, however, set the TD1 setting
greater than 1.00, except to allow a start with a longer than normal
accelerating time (e.g., high inertia motor application, emergency condition).
When TD1 is set greater than 1.00, use the speed switch (see
) to
provide locked rotor protection. See
for thermal overload limits for
selected settings. Refer to
through
in
Appendix F: Motor Thermal Element
for these and additional curves.
Figure 4.1
Thermal Overload Limits (Rating Method)
NOTE:
For IEC applications, set
SF = 1.05 or higher, but no higher
than 1.2.
RTC
TD
0.2
+
(
)
LRTHOT
•
60
ln
LRA
2
0.9
SF
•
(
)
2
–
LRA
2
SF
2
–
-------------------------------------------------
•
------------------------------------------------------------------------
=
RTC1
39 minutes
=
Cooltime
117 minutes
≥
Thermal Overload Limits
(Rating Method)
1
10
100
1000
10000
100000
1.00
10.00
100.00
Multiples of Full-Load Amps
Tr
ip
Ti
m
e
s
i
n
S
e
c
onds
600
300
150
75
40
20
10
5
LRTHOT
Thermal Overload Limits
(Rating Method)
1
10
100
1000
10000
100000
1.00
10.00
100.00
Multiples of Full-Load Amps
Tr
ip
Ti
m
e
s
i
n
S
e
c
onds
600
300
150
75
40
20
10
5
LRTHOT
(A) Service Factor = 1.01
(B) Service Factor = 1.15
1. Trip times are for Hot rotor and Hot stator
2. Relay Settings:
Thermal
Method
:=
Rating
Acceleration
Factor,
TD
:=
1.00
Run
Time
Constant,
RTC
:=
Auto
Locked
Rotor
Amps,
LRA
:=
6.0
Locked Rotor Time, LRTHOT (see the curves)
1. Trip times are for Hot rotor and Hot stator
2. Relay Settings:
Thermal
Method
:=
Rating
Acceleration
Factor,
TD
:=
1.00
Run
Time
Constant,
RTC
:=
Auto
Locked
Rotor
Amps,
LRA
:=
6.0
Locked Rotor Time, LRTHOT (see the curves)
Summary of Contents for SEL-749M
Page 6: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 14: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 20: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 32: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 52: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 118: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 188: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 216: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 224: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 274: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 286: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 306: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 310: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 314: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...