Date Code 20010719
701 Motor Protection Relay
Modbus
®
RTU Communications Protocol
05h Force Single Coil Command
C.9
05h Force Single Coil Command
The SEL-701 Relay uses this function code for a variety of data control purposes.
Specifically, you can use it to clear archive records, operate output contacts, and
operate breaker and remote bit elements.
Table C.8
05h Force Single Coil Command
The command response is identical to the command request.
The SEL-701 Relay offers the commands listed in
that you can execute
using function code 05h. The command coils are self-resetting.
Table C.9
SEL-701 Relay Command Coils
Table C.8
05h Force Single Coil Command
Bytes
Field
The Master Request Must Have the Following Format
1 byte
Slave address
1 byte
Function code (05h)
2 bytes
Coil reference
1 byte
Operation code (FF for bit set, 00 for bit clear)
1 byte
Placeholder (00)
2 bytes
CRC-16 for message
Table C.9
SEL-701 Relay Command Coils
Coil
Field
1 Start
2 Stop
3 Emergency
Restart
4
Reset Trip, Targets
Summary of Contents for SEL-701
Page 12: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 20: ...This page intentionally left blank ...
Page 36: ...This page intentionally left blank ...
Page 64: ...This page intentionally left blank ...
Page 144: ...This page intentionally left blank ...
Page 198: ...This page intentionally left blank ...
Page 232: ...This page intentionally left blank ...
Page 246: ...This page intentionally left blank ...
Page 346: ...This page intentionally left blank ...
Page 390: ...This page intentionally left blank ...
Page 408: ...This page intentionally left blank ...
Page 410: ......
Page 412: ......
Page 414: ......
Page 416: ......
Page 418: ......
Page 420: ......
Page 422: ......
Page 424: ......
Page 426: ......
Page 428: ......
Page 430: ......
Page 432: ......
Page 434: ......
Page 436: ......
Page 438: ......
Page 440: ......
Page 442: ......
Page 452: ...This page intentionally left blank ...