7.5
Date Code 20020903
SEL-587Z Instruction Manual
ASCII Command Reference
Command Definitions
CASCII Command
Access Levels 0, 1, 2
Display the SEL-587Z Compressed ASCII configuration message by typing:
CAS <CR>
The relay sends:
<STX>”CAS”,5,”YYYY”<CR>
“CST”,1,”YYYY” <CR>
“25H”,”MONTH”,”DAY”,”YEAR”,”HOUR”,”MIN”,”SEC”,”MSEC”,”87A”,’87B”,
“87C’,”IA”,”IB”,”IC”, ”MOF”,”+5V_PS”,”+5V_REG”,”-5V_REG”,”+10V_PS”,
”-10V_PS”,“VBAT”,”TEMP”,”RAM”,”ROM”,”CR_RAM”,”EEPROM”,”YYYY” <CR>
“1D”,”I”,”I”,”I”,”I”,”I”,”I”,”I”,”9S”,”9S”,”9S”,”9S”,”9S”,”9S”,”9S”,”9S”,”9S”,”9S”,
“9S”,”9S”,”9S”,”9S”,”9S”,”9S”,”9S”,”9S”,”YYYY” <CR>
“CHI”,1,”YYYY” <CR>
“10H”,”REC_NUM”,”MONTH”,”DAY”,”YEAR”,”HOUR”,”MIN”,”SEC”,”MSEC”,
“EVENT”,”TARGETS”,”YYYY” <CR>
“20D”,”I”,”I”,”I”,”I”,”I”,”I”,”I”,”I”,”6S”,”22S”,”YYYY” <CR>
“CEV”,1,”YYYY” <CR>
“1H”,”FID”,”YYYY”<CR>
”1D”,”40S”,”YYYY”<CR>
“7H”,”MONTH”,”DAY”,”YEAR”,”HOUR”,”MIN”,”SEC”,”MSEC”,”YYYY” <CR>
“1D”,”I”,”I”,”I”,”I”,”I”,”I”,”I”,”YYYY” <CR>
“6H”,”FREQ”,”SAM/CYC_A”,”SAM/CYC_D”,”NUM_OF_CYC”,”EVENT”, ”TARGETS”,”YYYY”<CR>
“1D”,”F”,”I”,”I”,”I”,”7S”,”22S”,”YYYY”<CR>
“8H”, “87A”,”87B”,”87C”,”IA”,”IB”,”IC”,”TRIG”,”
Names of Elements in Relay Word Rows 1 - 13
”,”YYYY”
<CR>
“60D”,”F”,”F”,”F”,”F”,”F”,”F”,”1S”,”26S”,”YYYY” <CR>
“CEV L”,1,”YYYY” <CR>
“1H”,”FID”,”YYYY”<CR>
”1D”,”40S”,”YYYY”<CR>
“7H”,”MONTH”,”DAY”,”YEAR”,”HOUR”,”MIN”,”SEC”,”MSEC”,”YYYY” <CR>
“1D”,”I”,”I”,”I”,”I”,”I”,”I”,”I”,”YYYY” <CR>
“6H”,”FREQ”,”SAM/CYC_A”,”SAM/CYC_D”,”NUM_OF_CYC”,”EVENT”, ”TARGETS”,”YYYY”<CR>
“1D”,”F”,”I”,”I”,”I”,”7S”,”22S”,”YYYY”<CR>
“8H”, “87A”,”87B”,”87C”,”IA”,”IB”,”IC”,”TRIG”,”
Names of Elements in Relay Word Rows 1 - 13
”,”YYYY”
<CR>
“120D”,”F”,”F”,”F”,”F”,”F”,”F”,”1S”,”26S”,”YYYY” <CR>
“CEV R”,1,”YYYY” <CR>
“1H”,”FID”,”YYYY”<CR>
”1D”,”40S”,”YYYY”<CR>
“7H”,”MONTH”,”DAY”,”YEAR”,”HOUR”,”MIN”,”SEC”,”MSEC”,”YYYY” <CR>
“1D”,”I”,”I”,”I”,”I”,”I”,”I”,”I”,”YYYY” <CR>
“6H”,”FREQ”,”SAM/CYC_A”,”SAM/CYC_D”,”NUM_OF_CYC”,”EVENT”, ”TARGETS”,”YYYY”<CR>
“1D”,”F”,”I”,”I”,”I”,”7S”,”22S”,”YYYY”<CR>
“8H”, “87A”,”87B”,”87C”,”IA”,”IB”,”IC”,”TRIG”,”
Names of Elements in Relay Word Rows 1 - 13
”,”YYYY”
<CR>
“256D”,”F”,”F”,”F”,”F”,”F”,”F”,”1S”,”26S”,”YYYY” <CR>
<ETX>
CEVENT
Command
Access Levels 1, 2
Display event report in Compressed ASCII format by typing:
CEV [
n x
] <CR>
The parameters in brackets, [ ], are optional.
n
is the number of the event report, as used in the
EVE
command.
x
= L specifies long event report, as used in the
EVE
command.
x
= R specifies raw (unfiltered) analog data, as used in the
EVE
command.
The relay responds to the
CEV
command with the
n
th event report as
shown below. Emphasized items are replaced with the actual relay data.
Summary of Contents for SEL-587Z
Page 10: ...This page intentionally left blank ...
Page 12: ...This page intentionally left blank ...
Page 66: ...This page intentionally left blank ...
Page 106: ...This page intentionally left blank ...
Page 126: ...This page intentionally left blank ...
Page 162: ...This page intentionally left blank ...
Page 228: ...This page intentionally left blank ...