IMPORTANT
: Single or multiple heater placement must be such that continu-
ous operation of heater(s) will not cause combustible material or materials in
storage to reach a temperature in excess of ambient temperature plus 90F°
(50C°).
It is the installer
’
s responsibility to ensure that building materials with a
low heat tolerance which may degrade at lower temperatures are protect-
ed to prevent degradation. Examples of low heat tolerance materials in-
clude vinyl siding, fabrics, some plastics, filmy materials, etc.
Refer to
“
Clearance to Combustibles
”
information on pages 6 to 8, and
Figure 1 and Table 1.
TABLE 2: GUIDELINES FOR HEATER PLACEMENT
MODEL
GUIDELINE*
MOUNTING
HEIGHT
ft
(m)
MAXIMUM
DISTANCE
BETWEEN
HEATERS
ft
(m)
DISTANCE –
OUTSIDE WALL
TO HEATER LONG AXIS
(PARALLEL TO WALL) IN
“
FEET
”
HORIZONTAL
ft
(m)
ANGLE
STS
-
JZ / IQ 200
18
–
30
(6
-
8)
50
(15)
17
–
25
(5
-
8)
COMBUSTIBLE
CLEARANCE
BEHIND
REFLECTOR
-
or greater
(refer to Table 1)
STS
-
JZ / IQ 175
18
–
30
(6
-
8)
50
(15)
17
–
25
(5
-
8)
STS
-
JZ / IQ 155
16
–
25
(5
-
7)
45
(14)
15
–
20
(5
-
7)
STS
-
JZ / IQ 130
15
–
21
(5
-
7)
40
(12)
15
–
20
(5
-
7)
STS
-
JZ / IQ 110
13
–
19
(4
-
6)
35
(11)
13
–
18
(4
-
6)
STS
-
JZ / IQ 100
15
–
19
(5
-
6)
35
(11)
13
–
18
(4
-
6)
STS
-
JZ / IQ 80
10
–
16
(3
-
5)
30
(9)
12
–
16
(4
-
5)
STS
-
JZ / IQ 60
8
–
14
(2.5
-
5)
25
(8)
11
–
15
(3.4
-
5)
STS
-
JZ / IQ 45
8
–
12
(2.5
-
4)
20
(6)
8
–
12
(2.5
-
4)
*
GUIDELINE MOUNTING HEIGHTS are typical to provide optimum comfort in general space
heating applications. Variance to these typical heights can occur in some applications:
•
Higher mounting heights due to structure or application requirements
•
Lower mounting heights: Area or
‘
spot
’
heat; locations with sufficient horizontal separa-
tion distance from personnel; areas with greater infiltration losses (near overhead doors,
etc)
MOUNTING
HEIGHT
ft
(m)
MAXIMUM
DISTANCE
BETWEEN
HEATERS
ft
(m)
DISTANCE –
OUTSIDE WALL
TO HEATER LONG AXIS
(PARALLEL TO WALL) IN
“
FEET
”
MODEL
“
Straight
”
or
“
U
-
Tube
”
HORIZONTAL
ft
(m)
ANGLE
STS
-
JZ / IQ 200
18
–
25
(6
-
8)
50
(15)
17
–
25
(5
-
8)
COMBUSTIBLE
CLEARANCE
BEHIND
(refer to Table 1)
STS
-
JZ / IQ 175
18
–
25
(6
-
8)
50
(15)
17
–
25
(5
-
8)
STS
-
JZ / IQ 155
16
–
21
(5
-
7)
45
(14)
15
–
20
(5
-
7)
STS
-
JZ / IQ 130
15
–
21
(5
-
7)
40
(12)
15
–
20
(5
-
7)
STS
-
JZ / IQ 110
13
–
19
(4
-
6)
35
(11)
13
–
18
(4
-
6)
STS
-
JZ / IQ 100
13
–
19
(4
-
6)
35
(11)
13
–
18
(4
-
6)
STS
-
JZ / IQ 80
10
–
16
(3
-
5)
30
(9)
12
–
16
(4
-
5)
STS
-
JZ / IQ 60
8
–
14
(2.5
-
5)
25
(8)
11
–
15
(3.4
-
5)
STS
-
JZ / IQ 45
8
–
12
(2.5
-
4)
20
(6)
8
–
12
(2.5
-
4)
7. GUIDELINES FOR HEATER PLACEMENT