Varistar LHX 3
60130-626 Revision 001
6
3. LHX
3
Technical Data
Technical Details
Usable cooling capacity (cooling water inlet temperature
10° C, air exit temperature 20° C)
kW
3
Cooling medium
Water
Water flow volume
m3/h
Up to max. 2.0
Pressure loss – system, measured at flow rate 0.5 m³/h
bar
0.1
Water circuit
Water inlet temperature (recommended)
°C
6 to 16
Air circuit
Airflow volume
m3/h
900
Electrical data AC
Supply voltage
1 / N
PE
230 V; 50/60 Hz
Current consumption
A
0.38
Power consumption
W
85
Apparent power consumption at full load
VA
120
Protection fuse
A
2
General Data
Type of protection of cabinet
IP
55
Ambient temperature during transport
°C
-25 to 70
Ambient temperature range outside cabinet during
operation
°C
5 to 70
Relative humidity level
%
5 to 95
Noise level at 100% fan capacity
dB(A)
45,2
Weight kg
150
Air/Water Heat Exchanger Dimensions
Height mm
199
Width mm
464
Depth
mm
425 (465 mm with handles)