VARISTAR LHX 20
Interfaces
Cooling module 60714-050
www.schroff.biz
19
R2.1, May 10, 2012
6 Interfaces
Situated beside the control and display unit are a D-sub 25 socket, a D-sub 9
connector and a RJ45 socket. Additional interfaces are provided on the control
board and can only be accessed by removing the front cover of the cooling
module. (See control board overview in the Appendix.)
Figure 5: Interfaces
6.1 Pinout of D-sub 25 socket
Name
Pin
Function
E11
pin 10 / pin 22
Digital input:when bridged > remote control on/off
E12
pin 11 / pin 24
Digital input: when bridged > request max. cooling output
E13
pin 13 / pin 25
Digital input: reserve
K4
pin 1 / pin 14
Relay output 1 A / 60 V, closes when power absent
K5
pin 2 / pin 15
Relay output 1 A / 60 V, closes when limit temperature value on sensors F1/F2
(outlet) is attained. Alarm threshold is set in PA0 (P10/P11).
K6
pin 3 / pin 16
Relay output 1 A / 60 V, closes when limit temperature value on sensor F5 (inlet)
is reached. Alarm threshold is set in PA0 (P14/P15).
K7
pin 4 / pin 17
Relay output 1 A / 60 V, closes when limit value of fan speed is reached.
Alarm threshold is set in PA0 (P21).
K8
pin 5 / pin 18
Relay output 1 A / 60 V, closes if common fault occurs
Summary of Contents for 60714-050