VARISTAR LHX 20
Commissioning
Cooling module 60714-050
www.schroff.biz
15
R2.1, May 10, 2012
5.4 Connecting to the electricity supply
Mains supply to the 230 V
AC
version is via a IEC320-C14 connector with cable
strain relief, situated on the bottom of the cooling module.
A suitable connecting cable (IEC320-C13 Schuko) is provided with the module.
All cooling modules must be protected by an external pre-fuse of
max. 10 A.
Hazardous voltage!
Under certain circumstances during commissioning, completion, maintenance
and service it is necessary to open the enclosure.
Some exposed parts may be under live voltage. These works must therefore
only be carried out by specially trained technical personnel.
Always disconnect the supply voltage before opening the module!
These cooling modules are designed for a 230 V
AC
mains supply
.
The control electronics and fans, however, operate from a 48 V
DC
supply. The
230 V
AC
version is fitted with a 230 V
AC
mains adaptor,
which is positioned in the cooling module beneath the heat exchanger.
If the cooling unit is to be used exclusively in telecommunications environments
(redundant -48 V
DC
power supply), please contact Schroff Service for further
information.
Attention!
If the connecting cable supplied is not suitable for your country, you should
only substitute a mains connector with protective earthing that is permitted for
your device and for use in your country.
Hazardous voltage!
When power is connected, the cooling module enters standby mode. Certain
parts inside the unit are however already live.
Always disconnect the supply voltage before opening the module!
When power is connected to the module the display shows "OFF".If this does
not occur, open the cover of the display unit and check the status of the circuit
breaker situated below.