Operating instructions

Safety relay module

SRB 301MC

SRB 301MC-ST

EN

Dual-channel control of a safety-related electronic 

(microprocessor-based) safety guard with p-type transistor 

outputs e.g. AOPDs to IEC 61496 (see Fig. 13)

•  Wire breakage and earth leakage in the control circuits are detected.

•  The safety-monitoring module therefore is not equipped with a cross-

wire short detection here. The safety-monitoring module therefore is 

not equipped with a cross-wire short detection here.

•  Category 3 – PL e to ISO 13849-1 possible.

•  If cross-wire shorts in the control circuits are detected by the safety 

guard:  

Control category 4 – PL e to ISO 13849-1 possible.

Dual-channel control of magnetic safety switches according to 

IEC 60947-5-3 (see Fig. 14)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the control circuits are not detected.

•  Category 3 – PL e to ISO 13849-1 possible.

Dual-channel control of magnetic safety switches according to 

IEC  60947-5-3 (see Fig. 15)

•  The control system recognises wire breakage and earth faults in the 

control circuit.

•  Cross-wire shorts between the control circuits are detected.

•  Category 4 – PL e to ISO 13849-1 possible.

The connection of magnetic safety switches to the 

SRB 301MC safety-monitoring module is only admitted 

when the requirements of the standard IEC 60947-5-3 are 

observed.

As the technical data are regarded, the following minimum 

requirements must be met: 

– switching capacity: min. 240 mW 

– switching voltage: min. 24 VDC 

– switching current: min. 10 mA

For example, the following safety sensors meet the 

requirements: 

– BNS 33-02Z-2187, BNS 33-02ZG-2187 

– BNS 260-02Z, BNS 260-02ZG 

– BNS 260-02-01Z, BNS 260-02-01ZG

When sensors with LED are wired in the control circuit 

(protective circuit), the following rated operating voltage must 

be observed and respected:  

–  24 VDC with a max. tolerance of –5 %/+20 %

 

–  24 VAC with a max. tolerance of –5 %/+10 %

 

Otherwise availability problems could occur, especially in 

series-wired sensors, where a voltage drop in the control 

circuit is triggered by LEDs for instance.

S12

+24V +24V

S22

nQS
QS

S12 S22

S11 S21

nQS
QS

S12 S22

S11 S21

nQS
QS

Fig. 13

Fig. 14

Fig. 15

8.4  Actuator configuration

Single-channel control (see Fig. 16)

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts.

•  If the feedback circuit  

is not required, establish a bridge.

•  

S

 = Feedback circuit

Dual-channel control with feedback circuit (Fig. 17)

•  Suitable for increase in capacity or number of contacts by means of 

contactors or relays with positive-guided contacts.

•  If the feedback circuit is not required, establish a bridge.

•  

S

 = Feedback circuit

X1

X2

13

14

K

A

K

A

K

A

S

L1

N

X1

X2

13

14

K

B

K

A

K

B

K

A

K

B

L1

N

K

A

S

Fig. 16

Fig. 17

Summary of Contents for SRB 301MC

Page 1: ...odule must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found...

Page 2: ...061 To determine the Performance Level PL to ISO 13849 1 1 of the entire safety function e g sensor logic actuator an assessment of all relevant components is required The entire concept of the contro...

Page 3: ...e enclosure slightly tilted forwards in the standard rail and push up until it latches in position To avoid EMC disturbances the physical ambient and operational conditions at the place where the prod...

Page 4: ...S12 14 24 34 S21 42 X2 A2 S22 41 X1 A1 S12 18 28 38 S22 45 X1 A1 nQS QS Fig 1 Fig 2 Fig 3 6 Set up and maintenance 6 1 Functional testing The safety function of the safety monitoring module must be te...

Page 5: ...l emergency stop circuit with command devices to ISO 13850 and IEC 60947 5 5 Fig 7 Wire breakage and earth leakage in the control circuits are detected Category 1 PL c to ISO 13849 1 possible Dual cha...

Page 6: ...toring module is only admitted when the requirements of the standard IEC 60947 5 3 are observed As the technical data are regarded the following minimum requirements must be met switching capacity min...

Page 7: ...ype test T V Rheinland Industrie Service GmbH Alboinstr 56 12103 Berlin ID n 0035 EC prototype test certificate 01 205 5035 01 16 Person authorised for the compilation of the technical documentation O...

Page 8: ...K A Schmersal GmbH Co KG M ddinghofe 30 42279 Wuppertal Germany Phone 49 202 6474 0 Telefax 49 202 6474 100 E Mail info schmersal com Internet www schmersal com...

Reviews: