18
Operating instructions
Solenoid interlock
AZM40
EN
Table 1: Diagnostic information of the safety switchgear
System condition
Magnet
control IN
(bistable)
LED
Safety outputs
Y1, Y2
Diagnostic
output
OUT
green
red
yellow
AZM40Z
AZM40B
Guard open
24 V
on
off
off
0 V
0 V
0 V
Door closed,
not locked
24 V
on
off
flashes
0 V
24 V
24 V
Door closed,
locking impossible
0 V
on
flashes
2)
flashes
0 V
24 V
0 V
Door closed and locked
0 V
on
off
on
24 V
24 V
24 V
Error warning
1)
0 V / 24 V
on
flashes
2)
on / flashes
24 V / 0 V
24 V
1)
0 V
Error
0 V / 24 V
on
flashes
2)
on / flashes / off
0 V
0 V
0 V
Error Mechanical overload
0 V
flashes
synchronously
flashes
synchronously
flashes
synchronously
0 V
0 V
0 V
Error in input circuit X1 and/or X2
0 V / 24 V
flashes
off
see section on
diagnosis LEDs
depending on system status
Pre-warning stage, service life
(95% service life)
0 V / 24 V
flashes
synchronously
flashes
synchronously
on / flashes / off
depending on system status
Maximum service life reached
0 V / 24 V
flashes
alternately
flashes
alternately
off
0 V
0 V
0 V
Additionally for variant I1/I2:
Teach-in procedure actuator
started
24 V
off
on
flashes
0 V
0 V
0 V
Only I2: teach-in procedure
actuator (release block)
24 V
flashes
off
off
0 V
0 V
0 V
1)
after 30 min: disabling due to fault
2)
refer to flash code
Table 2: Error messages / flash codes red diagnostic LED
Flash codes (red)
Designation
Autonomous
switch-off after
Error cause
1 flash pulse
Error (warning) at output Y1
30 min
Fault in output test or voltage at output Y1,
although the output is disabled.
2 flash pulses
Error (warning) at output Y2
30 min
Fault in output test or voltage at output Y2,
although the output is disabled.
3 flash pulses
Error (warning) cross-wire short
30 min
Cross-wire short between the output cables or fault at both outputs
4 flash pulses
Error (warning) temperature too high
30 min
The temperature measurement reveals an internal temperature
that is too high
5 flash pulses
Actuator fault
0 min
Incorrect or defective actuator
6 flash pulses
Internal error
0 min
Error at control inputs
7 flash pulses
Error, interlock actuator
0 min
Lock/release blocked
8 flash pulses
Error (warning) over/under voltage
30 min
Supply voltage not within specifications
Continuous red signal Internal error
0 min
Device defective
7. Set-up and maintenance
7.1 Functional testing
The safety function of the safety components must be tested.
The following conditions must be previously checked and met:
1. Check max. axial misalignment of actuator and solenoid interlock.
2. Check max. angular misalignment (see “Mounting” part)
3. Fitting and integrity of the cable connections.
7.2 Maintenance
In the case of correct installation and adequate use, the safety
switchgear features maintenance-free functionality. A regular visual
inspection and functional test, including the following steps, is
recommended:
• Check for a secure installation of the actuator and the solenoid
interlock
• Check max. offset of actuator unit and safety interlock as well as
max. tilt/rotation angle and adjust hexagon socket screw M4, if
necessary.
• Fitting and integrity of the cable connections.
• Check the switch enclosure for damages
• Remove soiling
Adequate measures must be taken to ensure protection
against tampering either to prevent tampering of the safety
guard, for instance by means of replacement actuators.
Damaged or defective components must be replaced.
After reaching the service life of 200,000 cycles, the safety
interlock can no longer be locked and must be replaced
together with the actuator.