Operating instructions

Solenoid interlock

AZM150

EN

The safety level of the unlock function is determined exclusively 

by the external safety power shutdown.

A1

A2

  

+24 VDC

PL ? 
PFH

d

 ?

  

0 VDC

Safety power 
shutdown

Solenoid 
interlock

Guard locking 
function

Fault exclusion with regard to wiring routing must be 

observed.

If for a certain application the power to unlock version of 

a solenoid interlock cannot be used, for this exception an 

interlock with power to lock can be used if additional safety 

measure need to be realised that have an equivalent safety 

level. 

3.  Assembly

3.1  General mounting instructions

Please observe the remarks of the standards 

EN ISO 12100, EN ISO 14119 and EN ISO 14120.

4 M5 holes are provided for mounting the enclosure. The solenoid 

interlock is double insulated. The use of an earth wire is not authorised. 

The solenoid interlock must not be used as an end stop. Any mounting 

position. The mounting position however must be chosen so that the 

ingress of dirt and soiling in the used opening is avoided. Unused 

actuator openings must be sealed with slot sealing plugs.

Detailed information on actuators with standard coding (not 

included in delivery) AZM150-B1, AZM150-B5 and AZM150-B6 

and their mounting can be found in the actuator operating 

instructions.

The insertion funnel on the head of the interlock allows insertion of a 

flexible actuator with an axial offset of ≤ ±1 and a height offset of ≤ ±1. 

The actuator must be inserted into the actuator head easily. For doors that 

do not ensure this is possible, a door catch must be installed to prevent 

damage to the device.

When used in ambient temperatures > 40°C, the solenoid 

interlock must be protected against contact with inflammable 

materials or inadvertent personal contact.

Choosing the actuating planes

Offsetting the actuating head enables actuation of 8 levels.

1. Cover screws must be loosened

2. Remove cover

3. Turn actuating head to desired position

4.  Fit the cover and engage, tighten the cover screws (torque 0.5 Nm)

1.

4.

2.

3.

 

Do not lever out the side tabs. Levering out the tabs will 

damage the device.

 

3.2  Dimensions

All measurements in mm.

AZM150

with cover-side  

manual release

and rear  

manual release

10.8

48

40

30

144

204

7.5

19

24

19

5.4

Ø5.2

85.5

Ø 14.3

81.4

10.8

48

40

30

144

204

7.5

19

24

19

5.4

Ø5.2

85.5

Ø 14.3

81.4

Summary of Contents for AZM150

Page 1: ...exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all pre...

Page 2: ...pose The solenoid interlock has been designed to prevent in conjunction with the control part of a machine movable safety guards from being opened before hazardous conditions have been eliminated The AZM150 solenoid interlocks with individual coding offer a higher protection against tampering and remain off when the guard system is unlocked or open Interlocks with power to lock principle may only ...

Page 3: ...on category AC 15 DC 13 Rated operating current voltage Ie Ue 4 A 230 VAC 4 A 24 VDC Rated impulse withstand voltage Uimp 4 kV Rated insulation voltage Ui 300 V Thermal test current Ithe 5 A Max fuse rating 6 A gG Required rated short circuit current 1 000 A Rated control voltage Us 24 VDC 110 VAC 230 VAC Electrical data Magnet control Magnet switch on time 100 Power consumption max 8 5 W Accepted...

Page 4: ...gs must be sealed with slot sealing plugs Detailed information on actuators with standard coding not included in delivery AZM150 B1 AZM150 B5 and AZM150 B6 and their mounting can be found in the actuator operating instructions The insertion funnel on the head of the interlock allows insertion of a flexible actuator with an axial offset of 1 and a height offset of 1 The actuator must be inserted in...

Page 5: ...ting or welding the insertion depth of the actuator is not modified There are different actuator types available The actuators AZM150 B1 and AZM150 B5 are preferably used for sliding and removable safety guards For hinged guards the AZM150 B6L or AZM150 B6R actuator When the switch is fitted on a hinged safety guard please ensure that the point of rotation is located within the range of the upper ...

Page 6: ...ectrical connection 4 1 General information for electrical connection The electrical connection may only be carried out by authorised personnel in a de energised condition If the risk analysis indicates the use of a monitored interlock they are to be connected in the safety circuit with the contacts indicated with the symbol Appropriate cable glands with a suitable degree of protection are to be u...

Page 7: ...3 3 4 4 11 5 Set up and maintenance 5 1 Functional testing The safety function of the safety components must be tested The following conditions must be previously checked and met 1 Fitting of the solenoid interlock and the actuator 2 Check the integrity of the cable entry and connections 3 Check the switch enclosure for damage 4 Check that both the cover side and rear manual releases are in the st...

Page 8: ...Directives Machinery Directive EMC Directive RoHS Directive 2006 42 EC 2014 30 EU 2011 65 EU Applied standards EN 60947 5 1 2017 EN ISO 14119 2013 Person authorised for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal Place and date of issue Shanghai April 1 2021 Authorised signature Michele Seassaro Managing Director EU Declaration of conformity Original...

Reviews: