DESCRIPTION OF FUNCTIONS
44 | EN
6.3.5 Setting for the permitted leakage
The permitted leakage is set in mbar/s. The leakage after the control function interrupts the suction
because switching point H1 was reached is measured.
ISDU
Dec
Parameter
Description
108
Permitted leakage
Leakage after reaching H1
6.3.6 Counters
Each ejector has two internal counters that cannot be deleted and two internal counters that can be
deleted.
ISDU
Dec
Description
140
Counter for suction cycles (suction signal)
141
Counter for suction valve switching frequency
143
Counter for suction cycles (suction signal)
– can be deleted
144
Counter for suction valve switching frequency
– can be deleted
The deletable counters can be reset to 0 during operation via IO-Link using the appropriate system
commands.
The non-volatile storage of the counter statuses only occurs every 256 steps. That
means that when the operating voltage is switched off, up to 255 steps of the
counter are lost.