IO-Link Data Dictionary
SCPSi series
21.10.01.00065/02
29.08.2014
J. Schmalz GmbH
Aacher Straße 29, D 72293 Glatten
Tel.: +49(0)7443/2403-0
Fax: +49(0)7443/2403-259
[email protected]
78
0x004E dCS
1 byte
0 - 1
rw
0
0 = off
1 = on
100
0x0064 H-1
2 bytes
998 >= H1 >= (H2+h1)
rw
750
Unit: 1 mbar
101
0x0065 h-1
2 bytes
(H1-H2 >= h1 > 10
rw
150
Unit: 1 mbar
102
0x0066 H-2
2 bytes
(H1-h1 >= H2 >= (h2+2)
rw
550
Unit: 1 mbar
103
0x0067 h-2
2 bytes
(H2-2) >= h2 >= 10
rw
10
Unit: 1 mbar
106
0x006A tbL
2 bytes
100 - 9999
rw
200
Unit: 1 ms
107
0x006B t-1
2 bytes
0, 10 - 9999
rw
2000
Unit: 1 ms
108
0x006C -L-
2 bytes
1 - 999
rw
250
Unit: 1 mbar/sec
180
0x00B4
1 byte
0 - 2
rw
1
181
0x00B5
1 byte
0 - 1
rw
0
182
0x00B6
2 bytes
998 >= H1 >= (H2+h1)
rw
750
183
0x00B7
2 bytes
(H1-H2 >= h1 > 10
rw
150
184
0x00B8
2 bytes
(H1-h1 >= H2 >= (h2+2)
rw
550
185
0x00B9
2 bytes
(H2-2) >= h2 >= 10
rw
10
186
0x00BA
2 bytes
100 - 9999
rw
200
187
0x00BB
2 bytes
0, 10 - 9999
rw
2000
188
0x00BC
2 bytes
1 - 999
rw
250
200
0x00C8
1 byte
0 - 2
rw
1
201
0x00C9
1 byte
0 - 1
rw
0
202
0x00CA
2 bytes
998 >= H1 >= (H2+h1)
rw
750
203
0x00CB
2 bytes
(H1-H2 >= h1 > 10
rw
150
204
0x00CC
2 bytes
(H1-h1 >= H2 >= (h2+2)
rw
550
205
0x00CD
2 bytes
(H2-2) >= h2 >= 10
rw
10
206
0x00CE
2 bytes
100 - 9999
rw
200
207
0x00CF
2 bytes
0, 10 - 9999
rw
2000
Hysteresis h1
Setpoint H1
Disable continuous suction
Setpoint H2
Hysteresis h2
Setpoint H2
Hysteresis h2
Duration automatic blow
Permissible evacuation time
Hysteresis h2
Setpoint H2
Hysteresis h1
Permissible leakage rate
Permissible leakage rate
Production Setup - Profile P1
Air saving function
Disable continuous suction
Setpoint H1
Hysteresis h1
Profile P-2
(selected by PD Out 0 - Profile-Set = 2)
Setpoint H1
Duration automatic blow
Permissible evacuation time
Disable continuous suction
Duration automatic blow
Profile P-1
(selected by PD Out 0 - Profile-Set = 1)
Permissible evacuation time
Production Setup - Profile P2
Air saving function
J. Schmalz GmbH
4 of 11
SCPSi Data Dictionary