automatic cable rewinder FT 038 e-mobility with integrated charging electronic 

installation and operating instruction 

 

 

 

 

 

installation

 and operation instruction FT 038 e-mobility miL - A4 -

 version B

 

Seite 5 

11.03.2021 

Schill GmbH & Co. KG; Bruckstraße 44; 70734 Fellbach 

www.schill.de

 

ATTENTION 

 

Observe installation instructions 

 

According to DIN VDE 0100-722 (VDE 0100-722): 2013-01, a separate circuit must 
be set up for each charging socket (IEC 60364-7-722: Low-voltage electrical 
installations - Part 7-722: Requirements for special installations or locations - 
supply of electric vehicle) 

 

Protection via residual current device (RCD) at least type A, which switches off 
with AC or pulsating residual current with I

Δn ≥ 30mA 

 

If DC fault currents I

Δn ≥ DC 6mA can occur due to insulation faults in the 

charging circuit, a residual current device (RCD) type B is required or suitable 
pro

tective measures for DC fault currents ≥ DC 6mA must be provided (e.g. DC 

residual current monitoring device). 

EXTENSION CABLE 

The included standard cables are designed to tolerate the weight of the pulled-out cable 
including the cable stopper. Additional weights are not allowed. The mounted cables are 
limited to the specified lengths. Never use excessive force to unwind the cable as this can 
damage both the cable and the reel. Should the cable be blocked while coiling up, please 
pull the cable out again an

d recoil. Attention should also be paid to section „GENERAL". 

If the cable is damaged, please contact us (see "CONTACT"). 

FUSE / THERMAL SAFETY GUARD 

The integrated charging electronics is protected with a 5x20 glass bulb fuse. Accessible 
from the outside, this is located on the operating and signaling devices on the front of the 
charger. To change the fuse, remove the cap of the fuse holder the glass bulb fuse can 
then be replaced. 

The series of these automatic cable reels with integrated charging electronics is 
dimensioned in such a way that no excessive heat is generated when the cable is reeled 
or unreeled. For protection in case of unusual heat development, a self-holding or self-
switching temperature switch is installed, depending on the version. In the event of 
tripping, the charging of the electrically powered vehicle is interrupted. After a cooling 
phase, the temperature switch switches itself on or is reactivated by pressing the red 
temperature switch. Charging operation is resumed (see also "OPERATING AND 
MESSAGE ELEMENTS"). 

READY FOR USE 

Before commissioning, please conduct an electrical check according to VDE 0100 or to the 
respective national standard. Check that the end of the pull-out cable is correctly fitted with 
a charging socket. After connecting to the power supply (see "CONNECTING"), the cable 
reel should be live and ready for use. 

If this is not the case, the fuse and thermal safety guard must be checked (see "FUSE / 
THERMAL SAFETY GUARD"). 

Summary of Contents for FT 038 e-mobility

Page 1: ...obility with integrated charging electronic installation and operating instruction installation and operation instruction FT 038 e mobility miL A4 version B Seite 1 11 03 2021 Schill GmbH Co KG Bruckstraße 44 70734 Fellbach www schill de ...

Page 2: ... adapted to a changing parking situation There is no cable chaos no tripping hazard anymore If the charging connection is no longer needed a short pull on the cable stopper will suffice and the cable will roll up neatly The automatic cable rewinder ensures safety and order HANDLING The coiled cable should be pulled out to the required length against the spring tension but please refrain from the u...

Page 3: ... cable length A reduction of the spring load may affect the rewind function of the reel ATTENTION Do not release the cable when rewinding the tension of the spring can accelerate the winding speed to such a degree that the swinging cable end could cause injury Also damage to the cable and spring could be the result of such an action CABLE STOPPER The length of the available cable can be individual...

Page 4: ...ocking the cable in position The cable can be disengaged by gently continuing to pull the cable until the click can no longer be heard The loaded spring will pull the cable back onto the reel The locking device can be disengaged by pulling the knurled grip out by approx 1cm and turning it between 90 and180 This will disengage the locking device the cable is then constantly under tension ATTENTION ...

Page 5: ...blocked while coiling up please pull the cable out again and recoil Attention should also be paid to section GENERAL If the cable is damaged please contact us see CONTACT FUSE THERMAL SAFETY GUARD The integrated charging electronics is protected with a 5x20 glass bulb fuse Accessible from the outside this is located on the operating and signaling devices on the front of the charger To change the f...

Page 6: ... signals operational readiness If this is not the case the fuses must be checked Observe the description under OPERATING AND SIGNALING ELEMENTS If the charging electronics are equipped with an AC DC sensitive residual current monitoring device this must be checked for proper function before each charging process It is necessary that the charging process is deactivated no vehicle connected Observe ...

Page 7: ...Different flashing frequencies of the indicator light is shown the status of the charging controller flashing frequency meaning 1x fast pause No vehicle detected standby 2x fast pause Vehicle detected 1x long pause Vehicle requests charging contactor is ON 20x fast in 0 5 sec The current setting mode is called up or exited 1x each 0 3 sec Current setting mode one more amper set error states no cha...

Page 8: ...ut must be reset manually using the pushbutton The error storage can optionally be switched off then the reset takes place automatically as soon as the residual current fulfills the connection condition THERMAL SWITCH Switches off the charging process when a critical temperature is reached If the electronics of the automatic cable winder are defective please contact us see CONTACT TECHNICAL DATA T...

Page 9: ...V 400V AC Maximum charging current A 16 32 Maximum charging power kW 3 6 7 4 1ph 11 22 3ph Communication EV according to IEC 61851 1 mode 3 The stated operating temperatures relate only to the standard cable reel as described above and do not apply to e g plug in device They are only as an exception part of the delivery Specification for plug in devices can be found within the relevant standard DI...

Page 10: ... INSTRUCTION Wall installation with universal holder WB038 The cable reel can be rotated 150 Depending on the mounting height the rotatable roller guide can be adjusted to the cable pull direction and fixed Mounting fixture WB 038 for wall installation Ceiling installation rotating DB 038 Mounting fixture WB 038 is included in the scope of supply but no fastening screws Mounting fixture DB 038 and...

Page 11: ...If repeated over tightening the connection cable can be mechanically stressed and torn off TIGHTENING TORQUE Gehäuseschrauben Cover screws 0 8 Nm Sicherungsschraube M8 Locking screw M8 0 8 Nm Zugentlastung Strain relief 0 8 Nm Kabelstopper Cable stopper 0 8 Nm Schraubenmutter M30 Screw nut M30 40 Nm Kabelverschraubung Cable gland 2 5Nm Elektrische Anschlüsse Electrical connections 0 5 Nm MS Schlei...

Page 12: ...ntegrated charging electronic installation and operating instruction installation and operation instruction FT 038 e mobility miL A4 version B Seite 12 11 03 2021 Schill GmbH Co KG Bruckstraße 44 70734 Fellbach www schill de DIMENSION FT 038 05XX IXX ...

Page 13: ...spare parts please contact our local distribution partner or give us a ring on 0049 711 578807 0 or send a mail at sales schill de Please have the product number or the part number ready CONTACT Administration Fellbach Schill GmbH Co KG Bruck Straße 44 70734 Fellbach Telefon 49 0 711 578807 0 Telefax 49 0 711 578807 44 E Mail ino schill de Manufacture Laichingen Schill GmbH Co KG Hirschstr 81 8915...

Reviews: