20 Technical data
20.8
Mode of operation CM03 + QT
ON-OFF & INCHING operation
CM03 + QT12
CM03 + QT25
CM06 + QT50
S2 - 15 minutes according to IEC
60034
S2 - 15 minutes according to IEC
60034
S2 - 15 minutes according to IEC
60034
2,5 - 10 RPM
2,5 - 20 RPM
2,5 - 20 RPM
M
max
= 120 Nm
M
max
= 250 Nm
M
max
= 500 Nm
M
avg
= 60 Nm
M
avg
= 125 Nm
M
avg
= 160 Nm
Life time*
10.000 cycles
10.000 cycles
10.000 cycles
MODULATING operation
CM03 + QT12
CM03 + QT25
CM06 + QT50
S4 - 1.200 c/h - max. 50% DC
according to IEC 60034
S4 - 1.200 c/h - max. 50% DC
according to IEC 60034
S4 - 1.200 c/h - max. 50% DC
according to IEC 60034
2,5 - 10 RPM
2,5 - 20 RPM
2,5 - 20 RPM
M
max
= 120 Nm
M
max
= 250 Nm
M
max
= 500 Nm
M
avg
= 60 Nm
M
avg
= 125 Nm
M
avg
= 250 Nm
Life time*
1.800.000 starts
1.200.000 starts
1.200.000 starts
CONTINUOUS MODULATING operation
CM03 FS 30/5
CM03 FS 50/8
CM03 FS 100/12
S9 - 1.800 c/h according to IEC
60034
S9 - 1.800 c/h according to IEC
60034
S9 - 1.800 c/h according to IEC
60034
2,5 - 10 RPM
2,5 - 20 RPM
2,5 - 20 RPM
M
max
= 120 Nm
M
max
= 250 Nm
M
max
= 500 Nm
M
avg
= 40 Nm
M
avg
= 80 Nm
M
avg
= 160 Nm
Life time*
1.800.000 starts
1.200.000 starts
1.200.000 starts
*
NOTE:
life time is based on proper operation and maintenance according to SCHIEBEL operating manual
CYCLE
= movement of 90° in both directions with at least 30% of nominal toque and the ability to accept 100% of nominal
torque for at least 5% of the stroke
START
= movement of at least 1° of stroke in both directions with a load of minimum 30% of nominal torque
89