© Safety and Installation Guide – Edition Dec. 2010  Scheuten Solar USA, Inc.

 

All rights reserved. Specifications in this manual are subject to change without notice. 

 

2 of 5 

 

2.1 Bolting Mounting Method 

The factory mounting holes found in the long frame segments can be 
used (

see 

Figure 1- 

Mounting Specifications

) to secure the modules to 

suitable support structure. The frame must be secured at a minimum of 
four points when bolting. The modules are bolted from the backside as 
shown in 

Figure 2

. Scheuten recommends using four (4) M6 or ¼ in. 

stainless steel bolt assemblies to secure each module. Each assembly 
should consist of a bolt, washer, lock washer and nut. The ¼ in. (M6) 
bolting  assembly  should  be  secured  with  a  torque  wrench  to  a 
tightening torque of 9 ft-lbf (12 Nm).  
 

Figure 2

 – Bolting

 

 

 

1.- 

Bolt 

      

3.-

 

Lock Washer

 

2.-

 

Nut 

      

4.-

 

Washer

 

 

Table 1- 

Recommended Bolting Components 

Component 

Description 

Distributor 

Part Number 

Bolt 

¼” -20, SS 

McMaster-Carr 

92240A540 

Nut 

¼” -20, SS 

McMaster-Carr 

91847A029 

Washer 

ID .266”, OD .563”,SS 

McMaster-Carr 

90313A204 

Lock Washer 

¼” , SS 

McMaster-Carr 

92146A029 

See: www.mcmaster.com 

 

2.2 Mounting Using Topside Module Clamps 

Clamps  can  also  be  used  to  secure  modules  to  a  suitable  support 
structure.  When  using  clamps,  they  can  be  attached  at  the  position 
where  the  frame  holes  are  found.  The  dimensions  of  the  clamp 
surfaces  should  be  sized  adequately.  A  surface  area  of  at  least 
500 mm² (0.775 in

2

) is recommended. Module clamps and associated 

hardware assemblies must be compatible with other materials to avoid 
corrosion due to the use of dissimilar metals. 

 

Scheuten Solar recommends installing support rails at a distance 32 in. 
on-center  so  that  modules  may  be  clamped  to  support  rails  at 
approximately  16  in.  from  module  edge.  This  clamping  location 
coincides with the approximate location of the module mounting holes 
shown  in 

Figure  1.

  Modules  are  to  be  secured  to  the  support  rails 

using topside module clamps which do not shade the module. Clamps 
should be secured to a tightening torque of 20 ft-lbf. (28 Nm) for a 5/16 
in. stainless steel bolt. The support structure and clamps must have a 
design load of at least 75 psf (3600 Pa). 

The  loads  detailed  in  this  guide  apply  to  the  mounting  methods 
specified  above.  In  appendix  2  other  regular  mounting  methods  are 
described  with  different  load  regimes.  For  permission  to  mount 
Scheuten modules using specialized PV mounting systems other than 
those outlined above or in appendix 2, please contact Scheuten Solar. 
Failure to do so will void the warranty and panel certification.  

 

2.3 Additional information 

Scheuten PV modules may not be used as overhead glazing. In case 
of rooftop systems, fire protection must be compatible with the class C 
fire  rating  of  the  modules.  Forces  impacting  the  frame  profile  at  the 
points  of  contact  must  not  result  in  any  deformation  of  the  frame. 
Crowding  between  frame  and  glass  should  be  avoided  at  all  costs.  If 
installed on an incline, the modules should be secured from sliding at 
the eaves. Drainage openings must not be covered up.  No additional 
holes should be drilled into the unit for mounting purposes, for potential 
equalization  or  for  any  other  purposes.  Any  changes  of  this  kind  will 
void the warranty. 

3.0 Electrical Installation 

Danger!

  Risk  of  death  or  serious 

injury from electric shock! Do not 
connect  or  disconnect  modules 
under load.  

 

Scheuten  PV  modules  may  be  used  in  systems  that  are  accessible 
without  restrictions  if  installed  in  accordance  with  instructions 
(application  class  A,  IEC  61730  or  safety  class  II,  IEC  61140). 
Additionally, installation shall be in accordance with CSA C22.1, Safety 
Standard for Electrical Installations, Canadian Electrical Code, Part 1. 

  

 

Despite  protection  against  accidental  contact,  under  unfavorable 
conditions  if  several  modules  are  connected  in  series,  hazardous 
voltage of several hundred volts may be present during installation. For 
this reason, work on the modules may only be performed by qualified 
skilled  professionals.  The  manufacturer’s  instructions  of  the  other 
components  being  used,  especially  those  of  the  inverter,  are  to  be 
observed.  

 

Danger!

  Risk  of  death  or  serious 

injury from electric arcs!

  

 

Exposed  to  light  under  load  and  especially  in  the  event  of  a  short 
circuit,  high  levels  of  direct  current  can  result  in  dangerous  electric 
arcs,  if,  for  example,  the  connection  between  two  PV  modules  is 
separated.  
 
The  unit  may  only  be  connected  to  the  main  power  supply  by  a 
licensed  skilled  professional.  Work  to  be  performed  is  to  be 
coordinated  with  the  electricity  network  provider.  The  photovoltaic 
system must  be  approved  by  an  electrician  who  is  responsible  to  the 
operator and the local electricity company for assuring installation was 
carried out correctly.  

 
3.1 Junction box 

The junction box is of protection class IP 65. Observe the details listed 
on the cover. The box cover may only be opened in exceptional cases 
and exchange of parts in and on the junction box is only allowed by a 
skilled electrician authorized by Scheuten Solar. 
Within the junction box are the bypass diodes, Diotec type SB1240

1

.  

 

 

3.2 Connection cables and plug-in connectors  

The integrated connection cables are dual insulated and UV resistant. 
The wire diameter of the connection cables is 6 mm² (0.0093 in

2

). For 

wiring,  the  connection  cables  have  pre-assembled  plug-in  connectors 
with  reverse  polarity  protection.  Because  of  its  safe  design  features, 
accidental contact with current-carrying cables can be ruled out entirely 
when used correctly. When connected, protection class IP 65 applies. 
The  connectors  may  only  be  plugged  in  when  dry.  Special  attention 
should be given to assure a seamless connection.  
In  general,  the  connection  cable  should  not  be  subject  to  any  tensile 
loads.  Wires  should  be  attached  to  the  mounting  system  using  UV 
resistant  cable  ties  to  avoid  chafe  marks  from  movements  or  tensile 
loads. 

 
3.3. Module Connection 

Modules  may  be  connected  in  series  (voltage  additive)  and/or  in 
parallel (current additive) to produce the appropriate electrical output.  
PV module interconnections should be 90ºC wet-rated conductors. An 
allowable  wire type is using USE-2 or PV single-wire conductor cable 
for exposed applications. For field connections use insulated minimum 
no.12 AWG copper wires rated for a minimum of 90ºC. 

                                                 

1

 www.diotec.com/pdf/sb1220.pdf

 

Summary of Contents for Solar Fusion P6-60 U

Page 1: ...sk of electric shock Do not stand on drop scratch or allow objects to fall on modules Do not install or handle the modules when they are wet or during periods of high wind The applicable regulations pertaining to work safety accident prevention and securing the construction site must be observed Persons and objects have to be secured against falling Any third party need to be protected against inj...

Page 2: ...hould be drilled into the unit for mounting purposes for potential equalization or for any other purposes Any changes of this kind will void the warranty 3 0 Electrical Installation Danger Risk of death or serious injury from electric shock Do not connect or disconnect modules under load Scheuten PV modules may be used in systems that are accessible without restrictions if installed in accordance ...

Page 3: ...nding Lug Lay In Lug Ilsco GBL 4DBT Bolt 6 32 SS McMaster Carr 92314A148 Serrated Washer M5 SS McMaster Carr 91120A140 Washer ID 9 64 OD 3 8 SS McMaster Carr 92141A007 Nut 6 32 SS McMaster Carr 91841A007 See www ilsco com www mcmaster com Scheuten Solar recommends using a UL listed lay in ground lug such as IIsco GBL 4DBT or equivalent and stainless steel hardware bolt washer serrated washer and n...

Page 4: ...to 85 C 40 F up to 185 F Maximum system voltage 600 V Reverse current rating 15 A in accordance with IEC 61730 2 UL certified design load 75 PSF 3600 Pascal Recommended number of modules for series connection 12 Recommended number of modules for parallel connection 3 Only modules of the same output class may be connected to each other UL listed line fuses must be sized according to the reverse cur...

Page 5: ...pressure load psf 4 Clamps at long side Mounting holes A B 4 75 75 112 5 4 Clamps at long side Mounting holes A 4 B 12 and clamps separation 31 5 33 50 50 75 4 Clamps at long side Corner 4 50 50 75 4 Clamps at short side Corner 4 50 50 75 Line support on short side Short side Full support 50 50 75 Recommendations for mounting clamps C A B B Alternative clamping methods Length inch 2 6 Min frame ov...