background image

 
 

  

 

 

© Safety and Installation Guide – Edition Dec. 2010  Scheuten Solar USA, Inc.

 

All rights reserved. Specifications in this manual are subject to change without notice. 

 

3 of 5 

 

When connecting modules in parallel, each module (or series string of 
modules so connected) shall be connected according to the maximum 
series fuse as specified. Applicable regulations should be observed to 
assure  safety  and  maintain  the  warranty  when  working  with  electrical 
devices. A maximum system voltage of 600 V must not be exceeded, 
not even at especially low temperatures.  

 

Depending  on  its  set-up  location  and  environmental  conditions,  a  PV 
module  may  supply  higher  voltages  and  /  or  higher  current  when 
compared  to  standard  testing  conditions.  For  this  reason,  in  order  to 
define the rated voltage values of components, rated current values of 
wires, the size of fuses and the design of control systems that are to be 
connected at the output of PV modules, the Isc and Voc values listed 
on the module and in the data sheet may need to be adjusted. Refer to 
Section  690-8  of  the  National  Electrical  Code  for  an  additional 
multiplying factor of 125% (80% derating) which may be applicable.   

 

Depending on the installation location, special protection may need to 
be taken against lightning and electrical surge. Tight parallel wiring of 
the  positive  and  negative  conductors  can  reduce  coupling  of 
interference currents. 

 
3.4 Grounding 

For safety reasons, ground the module frame or array before wiring the 
circuit  in  a  manner  that  is  in  accordance  with  NEC  requirements  for 
grounding solar electrical systems. When grounding, use material that 
is certified according to UL 1703. In addition, grounding hardware must 
be compatible with other materials to avoid corrosion due to the use of 
dissimilar  metals.  Grounding  should  only  be  performed  by  a  qualified 
electrician. Wiring shall be in accordance with the NEC and grounding 
method shall also be in accordance with the NEC, article 250 and any 
relevant local code and/or ordinance. Grounding method of the frame 
of arrays shall comply with NEC, article 250. 

 

Figure 3

 – Designated Grounding Holes 

 

It is critical that the grounding system be designed so that maintenance 
and/or  repair  work  of  one  module  in  the  circuit  will  not  interrupt  the 
grounding  of  any  of  the  other  modules.  Each  module  has  two 
designated 0.17” grounding holes in the frame, shown in 

Figure 3

, for 

use with appropriate grounding hardware (not provided).  

Table 2: 

Recommended Grounding Components  

Component 

Description 

Manufacturer/ 
Distributor 

Part Number 

Grounding Lug 

Lay-In Lug 

Ilsco 

GBL-4DBT 

Bolt 

#6-32, SS 

McMaster-Carr 

92314A148 

Serrated Washer 

M5, SS 

McMaster-Carr 

91120A140 

Washer 

ID 9/64”, OD 3/8”, SS 

McMaster-Carr 

92141A007 

Nut 

#6-32, SS 

McMaster-Carr 

91841A007 

See: www.ilsco.com; www.mcmaster.com

Scheuten Solar recommends using a UL listed lay-in ground lug such 
as IIsco GBL-4DBT or equivalent, and stainless steel hardware (bolt, 
washer, serrated washer and nut). A tooth washer (serrated washer) 
should be used between the grounding lug and the module frame 
because it is critical that the grounding hardware break through the 
anodizing layer and establish electrical connection with the aluminum 
frame. Grounding hardware for outdoor use should be stainless steel. 
See 

Table 2

 for a list of recommended components. The assembly 

must be torqued between 15 in-lbs to 20 in-lbs for #6-32 bolt. 

 

 
Scheuten  Solar  recommends  that  the  ground  lug  be  secured  using  a 
bolt,  washer,  serrated  washer  and  nut  assembly.  The  assembly  shall 
incorporate  some  type  of  locking  mechanism  (lock  washer,  lock  nut 
etc.)  to  maintain  tension  between  the  bolt  and  the  assembly.  The 
grounding  assembly should  be  designed  to  prevent components from 
wiggling  loose,  which  can  jeopardize  the  integrity  of  the  grounding 
system.  See  Figure  4  below  for  an  example  of  acceptable  means  of 
equipment  grounding.  Refer  to  NEC  article  690  on  grounding  PV 
arrays for specific requirements.  

 

 

Figure 4

 – Grounding Example Drawings 

 

 

 

1

.-

 Nut 

 

 

 

4

.-

 Washer 

2

.-

 Serrated Washer 

 

5

.-

 Bolt 

3

.-

 Ground Lug 

 
The  equipment  grounding  conductor  must  not  be  smaller  than  No.14 
AWG (2.1 mm

2

), must be sized according to the NEC and shall be of 

copper,  copper  alloy,  or  other  material  acceptable  for  use  as  an 
electrical  conductor.  Only  the  stainless  steel  set  screw  of  the  lay-in 
ground  lug  provided  by  the  supplier  of  the  grounding  material  should 
be used to securely attach the copper equipment grounding conductor. 
Any  UL  approved  PV  grounding  method  and  components  are  also 
acceptable for the US and Canada.  

4. Maintenance 

Generally  speaking,  solar modules  are maintenance free.  For smaller 
inclination  angles,  it  may  be  necessary  to  clean  the  modules  with 
plenty  of  clean  water.  Avoid  any  harsh  additives.  When  cleaning  the 
glass, typical cleaning tools may be used. Any dried dirt residue should 
not  be  scratched  or  scraped  off  using  sharp  tools.  Otherwise, 
scratches or tears may cause damage to the glass surface. Every once 
in  a  while,  the  modules  should  be  inspected  to  assure  they  are  in 
proper condition, correctly wired and mounted. While doing so, assure 
that they are still firmly attached and that there is no corrosion.

 

5. Liability 

For liability see the Scheuten Solar website: www.scheutensolar.com 
Revisions  relating  to  technical  improvements  and  enhancements 
reserved

 

Summary of Contents for Solar Fusion P6-60 U

Page 1: ...sk of electric shock Do not stand on drop scratch or allow objects to fall on modules Do not install or handle the modules when they are wet or during periods of high wind The applicable regulations pertaining to work safety accident prevention and securing the construction site must be observed Persons and objects have to be secured against falling Any third party need to be protected against inj...

Page 2: ...hould be drilled into the unit for mounting purposes for potential equalization or for any other purposes Any changes of this kind will void the warranty 3 0 Electrical Installation Danger Risk of death or serious injury from electric shock Do not connect or disconnect modules under load Scheuten PV modules may be used in systems that are accessible without restrictions if installed in accordance ...

Page 3: ...nding Lug Lay In Lug Ilsco GBL 4DBT Bolt 6 32 SS McMaster Carr 92314A148 Serrated Washer M5 SS McMaster Carr 91120A140 Washer ID 9 64 OD 3 8 SS McMaster Carr 92141A007 Nut 6 32 SS McMaster Carr 91841A007 See www ilsco com www mcmaster com Scheuten Solar recommends using a UL listed lay in ground lug such as IIsco GBL 4DBT or equivalent and stainless steel hardware bolt washer serrated washer and n...

Page 4: ...to 85 C 40 F up to 185 F Maximum system voltage 600 V Reverse current rating 15 A in accordance with IEC 61730 2 UL certified design load 75 PSF 3600 Pascal Recommended number of modules for series connection 12 Recommended number of modules for parallel connection 3 Only modules of the same output class may be connected to each other UL listed line fuses must be sized according to the reverse cur...

Page 5: ...pressure load psf 4 Clamps at long side Mounting holes A B 4 75 75 112 5 4 Clamps at long side Mounting holes A 4 B 12 and clamps separation 31 5 33 50 50 75 4 Clamps at long side Corner 4 50 50 75 4 Clamps at short side Corner 4 50 50 75 Line support on short side Short side Full support 50 50 75 Recommendations for mounting clamps C A B B Alternative clamping methods Length inch 2 6 Min frame ov...

Reviews: