© Safety and Installation Guide – Edition Dec. 2010  Scheuten Solar USA, Inc.

 

All rights reserved. Specifications in this manual are subject to change without notice. 

 

5 of 5 

 

Appendix 2. 

Additional mounting options approved by Scheuten Solar 

 

Mounting method  

Position 

Range (inch) 
for clamp midpoint 

Design Load 

(psf) 

Max suction load 

(psf) 

Max. pressure load 

(psf) 

4 Clamps at long side 

Mounting holes (A)  B < 4 

75 

75 

112.5 

4 Clamps at long side 

Mounting holes (A)  4<B<12 and 

clamps separation 31.5 - 33  

50 

50 

75 

4 Clamps at long side 

Corner 

< 4 

50 

50

 

75 

4 Clamps at short side 

Corner 

< 4 

50 

50

 

75 

Line support on short side   Short side 

Full support 

50 

50

 

75 

 

Recommendations for mounting clamps  

 

 

 

C

A

B

B

 

 

Alternative clamping methods 

Length (inch)  

2 – 6 

Min. frame overlap (inch) 

0.25 

Min. effective  clamped area (inch²) 

0.5 

Recommended clamped area (inch²)  

0.8 

Bolts (inch) 

5/16 (M8) 

Torque (ft-lbf) 

Approx. 20 

Summary of Contents for Solar Fusion P6-60 U

Page 1: ...sk of electric shock Do not stand on drop scratch or allow objects to fall on modules Do not install or handle the modules when they are wet or during periods of high wind The applicable regulations pertaining to work safety accident prevention and securing the construction site must be observed Persons and objects have to be secured against falling Any third party need to be protected against inj...

Page 2: ...hould be drilled into the unit for mounting purposes for potential equalization or for any other purposes Any changes of this kind will void the warranty 3 0 Electrical Installation Danger Risk of death or serious injury from electric shock Do not connect or disconnect modules under load Scheuten PV modules may be used in systems that are accessible without restrictions if installed in accordance ...

Page 3: ...nding Lug Lay In Lug Ilsco GBL 4DBT Bolt 6 32 SS McMaster Carr 92314A148 Serrated Washer M5 SS McMaster Carr 91120A140 Washer ID 9 64 OD 3 8 SS McMaster Carr 92141A007 Nut 6 32 SS McMaster Carr 91841A007 See www ilsco com www mcmaster com Scheuten Solar recommends using a UL listed lay in ground lug such as IIsco GBL 4DBT or equivalent and stainless steel hardware bolt washer serrated washer and n...

Page 4: ...to 85 C 40 F up to 185 F Maximum system voltage 600 V Reverse current rating 15 A in accordance with IEC 61730 2 UL certified design load 75 PSF 3600 Pascal Recommended number of modules for series connection 12 Recommended number of modules for parallel connection 3 Only modules of the same output class may be connected to each other UL listed line fuses must be sized according to the reverse cur...

Page 5: ...pressure load psf 4 Clamps at long side Mounting holes A B 4 75 75 112 5 4 Clamps at long side Mounting holes A 4 B 12 and clamps separation 31 5 33 50 50 75 4 Clamps at long side Corner 4 50 50 75 4 Clamps at short side Corner 4 50 50 75 Line support on short side Short side Full support 50 50 75 Recommendations for mounting clamps C A B B Alternative clamping methods Length inch 2 6 Min frame ov...

Reviews: