Instruction Manual and Installation Instructions LAS 1218-2
13
Date: 06.11.2014
810.523 BA / EN
3
4
1
2
Fig. 5
Connection Diagram, LAS 1218-2 Battery Charger to Living Area and Starter Battery
1
Fuse F1
2
Fuse F2
3
Living area battery
4
Starter battery
³
+ terminal of LAS 1218-2 living area battery (flat push-on contact 6.3 x
0.8) to F1 (flat push-on contact 6.3 x 0.8)
³
F1 (flat push-on contact 6.3 x 0.8) to + terminal of living area battery (ring
terminal, M6 or M8)
³
+ terminal of LAS 1218-2 starter battery (flat push-on contact 6.3 x 0.8)
to F2 (flat push-on contact 6.3 x 0.8)
³
F1 (flat push-on contact 6.3 x 0.8) to + terminal of starter battery (ring
terminal, M6 or M8)
³
Connection, LAS 1218-2 to living area or starter battery
F
-- terminal of LAS 1218-2 (flat push-on contact 6.3 x 0.8)
F
-- terminal of battery (ring terminal, M6 or M8)
³
Label the two fuses with stickers ”F1 -- living area battery” and ”F2 -- star-
ter battery”.
Y
The negative terminal (-- Pol) of the living area battery must be connec-
ted externally to the negative terminal (-- Pol) of the starter battery.