18
2019-08-07 / V1.0
Installation
Contactors C193/C294 – Installation and Maintenance Instructions
Connect the coil terminals
The control wires for the coil connection must be fitted
with appropriate flat receptacles (6.3 x 0.8 mm).
NOTICE
X
Bending of the coil terminals is not permissible!
X
Move and lay the control wires and flat recepta-
cles only in plugging direction, see
Fig. 10
and
Fig. 11
.
X
Attach the control wires mechanically, in order
to minimize retroactivities (e. g. shock, vibra-
tions) from the wires to the terminals.
X
Plug the prepared control wires with the flat re-
ceptacles (4) to both coil terminals A1 and A2 (5).
6.3 x 0.8 mm
5
4
Fig. 10: C193 series: Connect the coil terminals
6.3 x 0.8 mm
5
4
Fig. 11: C294 series: Connect the coil terminals