NRWG Multi-Leaf Damper Models JK-180MB / JK-190 

  

Technical 

documentation 

 

Capacity and classification  |   

 

Construction subject to change 

 

No return possible 

Version: 2016-08-02 | Document: 09/53 | Page  3 

CAPACITY AND CLASSIFICATION 

 

Summary 

The classifications for JK-180MB / JK-190 are highlighted in colour. 
 

Operational safety 

Snow load 

Low 

ambient temperature 

Wind load 

Resistance to heat 

Possible classes according to DIN EN 12101-2 

Re A* 

SL A* 

T A* 

WL A* 

B A* 

Re 50 

SL 0 

T 0°C 

WL 1500 

B 300 

Re 1000 

SL 125 

T -5°C 

WL 3000 

B 600 

SL 250 

T -15°C 

SL 500 

T -25°C 

SL 1000 

*) A is used as wild card for a certain value specified by the manufacturer 
 
 
 

Aerodynamically active opening area 

 

Geometric opening area multiplied by the flow rate coeffi-
cient 

 

Flow rate coefficient determined experimentally either di-
rectly or indirectly from the test results of NRWGs of dif-
ferent sizes or from scaled-down models 

 
 
 

Operational safety 

 

Proof that the NRWG opens and closes during the number 
of specified cycles 

 

The designations A, 50 and 1000 indicate how often the 
NRWG was opened in the initial test without external load. 

 

The functional position must be reached within 60 °sec. 

 

When used additionally for ventilation purposes, the func-
tional test must not be carried until the NRWG has been 
opened 10,000 times in the ventilation position. 

 
 

Snow load 

 

Proof that the NRWG opens and remains open under wind 
and snow loads 

 

Indicates the test snow load in Pa (N/m²) applied when the 
opening process is tested. 

 

When the inclination of the recommended minimum in-
stallation angle exceeds 45°, the NRWG may be assigned 
to class SL 0. 

 

 
 

Low ambient temperature 

 

Proof of reliable functioning of the opening mechanism of 
the NRWG at lower temperatures 

 

Indicates the temperature in °C at which the NRWG will be 
tested 

 

NRWGs are suitable for use in buildings in which the tem-
peratures exceed 0 °C. 

 

For T(00), no low temperature test is required. 

 
 

Wind load 

 

Proof that the NRWG when exposed to wind load remains 
intact, remains closed and can be opened to assume its 
functional position after the exposure to the wind load is 
over. 

 

Indicates the test load (wind load) in Pa applied during the 
test 

 

When exposed to the relevant wind load, the NRWG must 
not open and not exhibit any permanent deformation. 

 

Following the test, it must open within 60 sec. after being 
actuated. 

 
 

Resistance to heat 

 

Proof that the installed NRWG when exposed to fire will 
open within 60 sec. to assume its functional position and 
remain there. 

 

Indicates the temperature in °C at which the NRWG will be 
tested 

 
 
 
 

 
 

 

 

Summary of Contents for JK-180MB

Page 1: ...s 7 Cross sections and opening surface areas 8 Dimensions JK 180MB 9 Dimensions JK 190 10 Installation information 11 Installation JK 180MB 12 Installation JK 190 12 Installation accessories JK 190 13...

Page 2: ...o the measurement and installation of natural smoke removal systems NRA for rooms with ver tical smoke removal via the roof by thermal buoyancy ac cording to DIN 18232 1 for single storey buildings an...

Page 3: ...onally for ventilation purposes the func tional test must not be carried until the NRWG has been opened 10 000 times in the ventilation position Snow load Proof that the NRWG opens and remains open un...

Page 4: ...re jointly adjusted in opposite directions via external plastic gear wheels A cover plate protects the gear wheels from external con tamination and reduces the risk of injury to persons during assembl...

Page 5: ...e Version 2016 08 02 Document 09 53 Page 5 MODEL JK 180MB JK 190 Components of the multi leaf damper Size chart B and H components can be freely selected 1 Housing B part 2 Housing H part 3 Actuator s...

Page 6: ...0 Nm 230 V AC 2 3 point E24 20 Nm 24 V AC 2 3 point E25 20 Nm 24 V AC DC 0 10 V DC with RJ45 plug E72 20 Nm 24 V AC DC 0 10 V DC E73 Electrical with integrated limit switches accessories 2 limit switc...

Page 7: ...led Incl screw package for fastening to the NRWG damper Mounting bracket edge mounting EBW R H EBW R B Mounting bracket for fastening to ceiling on three sides and for fastening to wall on one side de...

Page 8: ...ND OPENING SURFACE AREAS GEOMETRIC OPENING SURFACE AREA AV FREE CROSS SECTION FQ FLOW RATE COEFFICIENT CV AERODYNAMICALLY ACTIVE OPENING SURFACE AREA AA AERODYNAMICALLY ACTIVE OPENING SURFACE AREA WIT...

Page 9: ...NRWG Multi Leaf Damper Models JK 180MB JK 190 Technical documentation Dimensions JK 180MB Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 9 DIMENSIONS JK 180MB...

Page 10: ...NRWG Multi Leaf Damper Models JK 180MB JK 190 Technical documentation Dimensions JK 190 Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 10 DIMENSIONS JK 190...

Page 11: ...mpair their permanent functioning They must be fastened by means of suitable mounting mate rials approved by the building supervisory authorities see Accessories in accordance with the mounting instru...

Page 12: ...No return possible Version 2016 08 02 Document 09 53 Page 12 INSTALLATION JK 180MB Fastening points If required the connecting cable of the actuator must be run through the opening provided in the mou...

Page 13: ...180MB JK 190 Technical documentation Installation accessories JK 190 Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 13 INSTALLATION ACCESSORIES JK 190 Support...

Page 14: ...le Version 2016 08 02 Document 09 53 Page 14 Mounting bracket edge mounting EBW R H EBW R B shown EBW R B Selection EBE R H fastened to the wall via the bracket on the H part of the multi leaf damper...

Page 15: ...JK 190 Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 15 Mounting bracket corner mounting EBW E L EBW E R Selection viewing direction from inside to outside E...

Page 16: ...ECTION HOOD Flat roof plinth with connection point on multi leaf damper Roof hood or louvre hood as weather protection Access possible to NRWG for maintenance and actuator replacement To be mounted be...

Page 17: ...ction hood Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 17 Plinth design rectangular JK 180MB square JK 190 Other dimensions on request Hood design Roof hoo...

Page 18: ...t SCHAKO type JK 180MB Nominal size x mm Aa m Empty space in the building shell x mm Installation position wall ceiling2 JK 190 NRWG multi leaf damper housing leakage class C and leak age with closed...

Page 19: ...0MB JK 190 Technical documentation Order details Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 19 ORDER DETAILS If no order details are given the model highl...

Page 20: ...NRWG Multi Leaf Damper Models JK 180MB JK 190 Technical documentation CE marking Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 20 CE MARKING JK 180MB JK 190...

Page 21: ...c requirements of ventilation and air conditioning systems Measurement methods and investigations during hygienic controls and hygienic in spections DIN EN 1751 Ventilation of buildings units of the a...

Reviews: