NRWG Multi-Leaf Damper Models JK-180MB / JK-190 

  

Technical 

documentation 

 

Specification texts  |   

 

Construction subject to change 

 

No return possible 

Version: 2016-08-02 | Document: 09/53 | Page  18 

SPECIFICATION TEXTS 

 

JK-180MB 

NRWG multi-leaf damper, housing leakage class C and leak-
age with closed damper leaf class 3 to DIN EN 1751, consist-
ing of a dimensionally stable profiled frame made of 1.5 mm 
galvanised sheet steel, frame depth 180 mm with joint flow-
favouring hollow-body blades adjustable in opposite direc-
tions made of torsion-resistant aluminium profile. 
 
The blades are adjusted by means of external plastic gear 
wheels arranged on one side. 

 

With sintered bearing 

 

TÜV inspected according to VDI 6022 Sheets 1+2 and DIN 
EN1751  

 

With mounting plate for flush-mounted installation in wall 
and ceiling

2)

 

 
Electric actuator with spring return (currentless OPEN) 

 

20 Nm, 230 V AC, 2/3-point (-E24) 

 

20 Nm, 24 V AC/DC, 2/3-point (-E25) 

 

20 Nm, 24 V AC/DC, 0-10 V DC with RJ45 plug(-E72) 

 

20 Nm, 24 V AC/DC, 0-10 V DC (-E73) 
 

Electric actuator with integrated limit switches 

 

2 limit switches, CLOSED and OPEN (-IS2) 
 

Direct-current actuator 

 

10 Nm, 24 V DC (-E70) 

 

10 Nm, 24 V DC with RJ45 plug (-E71) 

 
 
Accessories: 

 

Wall anchor package 1 (-M1) 

 

Roof hood / Louvre hood 

 
 
 
 
 
Tested and certified to DIN EN 12101-2 in at least the follow-
ing model: 

 

Re1000 

 

SL0, 

 

T(00) 

 

WL1500 

 

B300 

 

Type B with double function 

 
 
Product:   

 

SCHAKO type JK-180MB 

Nominal size: 

………….  x  ……….. mm,  
Aa =……………….… m² 

Empty space in the building shell: 

………….  x  ……….. mm 

Installation position: 

 

wall / ceiling

2)

 

 
 

 

JK-190 

NRWG multi-leaf damper, housing leakage class C and leak-
age with closed damper leaf class 3 to DIN EN 1751, consist-
ing of a dimensionally stable profiled frame made of 1.5 mm 
galvanised sheet steel, frame depth 190 mm with joint flow-
favouring hollow-body blades adjustable in opposite direc-
tions made of torsion-resistant aluminium profile. 
 
The blades are adjusted by means of external plastic gear 
wheels arranged on one side. 

 

With sintered bearing 

 

TÜV inspected according to VDI 6022 Sheets 1+2 and DIN 
EN 1751 

 

For mounting on wall and ceiling³ (surface mounting) 

 
 
Electric actuator with spring return (currentless OPEN) 

 

20 Nm, 230 V AC, 2/3-point (-E24) 

 

20 Nm, 24 V AC/DC, 2/3-point (-E25) 

 

20 Nm, 24 V AC/DC, 0-10 V DC with RJ45 plug(-E72) 

 

20 Nm, 24 V AC/DC, 0-10 V DC (-E73) 
 

Electric actuator with integrated limit switches 

 

2 limit switches, CLOSED and OPEN (-IS2) 
 

Direct-current actuator 

 

10 Nm, 24 V DC (-E70) 

 

10 Nm, 24 V DC with RJ45 plug (-E71) 

 
 
Accessories: 

 

Wall anchor package 2 (-M2) 

 

Wall anchor package 3 (-M3) 

 

Support sheet (-AB) 

 

Mounting bracket edge mounting (-EBW-R-H) / (-EBW-R-B) 

 

Mounting bracket corner mounting (-EBW-E-L)/(-EBW-E-R) 

 

Roof hood / Louvre hood 

 
Tested and certified to DIN EN 12101-2 in at least the follow-
ing model: 

 

Re1000 

 

SL0 

 

T(00) 

 

WL1500 

 

B300 

 

Type B with double function 

 
 
Product:   

 

SCHAKO type JK-190 

Nominal size: 

 

………….  x  ………..  mm, 

 

 

 

Aa = ……………….… m² 

Empty space in the building shell: 

………….  x  ……….. mm  

Installation position: 

 

wall / ceiling

2)

 

 
 
 

2) 

Weather protection must be taken into account 

 

 

 

Summary of Contents for JK-180MB

Page 1: ...s 7 Cross sections and opening surface areas 8 Dimensions JK 180MB 9 Dimensions JK 190 10 Installation information 11 Installation JK 180MB 12 Installation JK 190 12 Installation accessories JK 190 13...

Page 2: ...o the measurement and installation of natural smoke removal systems NRA for rooms with ver tical smoke removal via the roof by thermal buoyancy ac cording to DIN 18232 1 for single storey buildings an...

Page 3: ...onally for ventilation purposes the func tional test must not be carried until the NRWG has been opened 10 000 times in the ventilation position Snow load Proof that the NRWG opens and remains open un...

Page 4: ...re jointly adjusted in opposite directions via external plastic gear wheels A cover plate protects the gear wheels from external con tamination and reduces the risk of injury to persons during assembl...

Page 5: ...e Version 2016 08 02 Document 09 53 Page 5 MODEL JK 180MB JK 190 Components of the multi leaf damper Size chart B and H components can be freely selected 1 Housing B part 2 Housing H part 3 Actuator s...

Page 6: ...0 Nm 230 V AC 2 3 point E24 20 Nm 24 V AC 2 3 point E25 20 Nm 24 V AC DC 0 10 V DC with RJ45 plug E72 20 Nm 24 V AC DC 0 10 V DC E73 Electrical with integrated limit switches accessories 2 limit switc...

Page 7: ...led Incl screw package for fastening to the NRWG damper Mounting bracket edge mounting EBW R H EBW R B Mounting bracket for fastening to ceiling on three sides and for fastening to wall on one side de...

Page 8: ...ND OPENING SURFACE AREAS GEOMETRIC OPENING SURFACE AREA AV FREE CROSS SECTION FQ FLOW RATE COEFFICIENT CV AERODYNAMICALLY ACTIVE OPENING SURFACE AREA AA AERODYNAMICALLY ACTIVE OPENING SURFACE AREA WIT...

Page 9: ...NRWG Multi Leaf Damper Models JK 180MB JK 190 Technical documentation Dimensions JK 180MB Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 9 DIMENSIONS JK 180MB...

Page 10: ...NRWG Multi Leaf Damper Models JK 180MB JK 190 Technical documentation Dimensions JK 190 Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 10 DIMENSIONS JK 190...

Page 11: ...mpair their permanent functioning They must be fastened by means of suitable mounting mate rials approved by the building supervisory authorities see Accessories in accordance with the mounting instru...

Page 12: ...No return possible Version 2016 08 02 Document 09 53 Page 12 INSTALLATION JK 180MB Fastening points If required the connecting cable of the actuator must be run through the opening provided in the mou...

Page 13: ...180MB JK 190 Technical documentation Installation accessories JK 190 Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 13 INSTALLATION ACCESSORIES JK 190 Support...

Page 14: ...le Version 2016 08 02 Document 09 53 Page 14 Mounting bracket edge mounting EBW R H EBW R B shown EBW R B Selection EBE R H fastened to the wall via the bracket on the H part of the multi leaf damper...

Page 15: ...JK 190 Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 15 Mounting bracket corner mounting EBW E L EBW E R Selection viewing direction from inside to outside E...

Page 16: ...ECTION HOOD Flat roof plinth with connection point on multi leaf damper Roof hood or louvre hood as weather protection Access possible to NRWG for maintenance and actuator replacement To be mounted be...

Page 17: ...ction hood Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 17 Plinth design rectangular JK 180MB square JK 190 Other dimensions on request Hood design Roof hoo...

Page 18: ...t SCHAKO type JK 180MB Nominal size x mm Aa m Empty space in the building shell x mm Installation position wall ceiling2 JK 190 NRWG multi leaf damper housing leakage class C and leak age with closed...

Page 19: ...0MB JK 190 Technical documentation Order details Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 19 ORDER DETAILS If no order details are given the model highl...

Page 20: ...NRWG Multi Leaf Damper Models JK 180MB JK 190 Technical documentation CE marking Construction subject to change No return possible Version 2016 08 02 Document 09 53 Page 20 CE MARKING JK 180MB JK 190...

Page 21: ...c requirements of ventilation and air conditioning systems Measurement methods and investigations during hygienic controls and hygienic in spections DIN EN 1751 Ventilation of buildings units of the a...

Reviews: