NRWG Multi-Leaf Damper Models JK-180MB / JK-190
Technical
documentation
Installation information |
Construction subject to change
No return possible
Version: 2016-08-02 | Document: 09/53 | Page 11
INSTALLATION INFORMATION
The multi-leaf dampers must not be tilted during installation.
Otherwise, this may result in problems with the adjustment
mechanism or in leaks.
The multi-leaf dampers are delivered in open position (cur-
rentless OPEN) and must be mounted as such.
NRWGs must be installed such that external forces do not
impair their permanent functioning.
They must be fastened by means of suitable mounting mate-
rials approved by the building supervisory authorities (see
Accessories) in accordance with the mounting instructions.
Protection from weather conditions must be guaranteed on
site!
Fastening materials
Multi-leaf damper / Accessories - Masonry
Anchor bolt: drilling depth = 75 mm; drilling diameter =
8 mm
1 = Anchor bolt
2 = Washer
3 = Hexagon nut
4 = Spacer disc
5 = O-ring
Multi-leaf damper – Mounting plate (JK-180MB)
1 = Washer
2 = Allen screw
3 = Cage nut
4 = Sealing tape
Multi-leaf damper - Accessories (JK-190)
B and H sides
1 = Washer
2 = Allen screw
3 = Cage nut
4 = Sealing tape
Corner
1 = Washer
2 = Allen screw
3 = Hexagon nut
4 = Sealing tape
4
4
4
Sealing tape