Fire damper BKP-EN
Technical documentation
Models and dimensions
Construction subject to change.
No return possible!
Version: 2020-09-01 | Page 6
Use
The fire damper type BKP-EN can be fitted as shown in the following table.
Use
Installa-
tion
Material/Model
Minimum
thickness [mm]
Minimum distance
[mm]
Fire resistance
class
Notes
Page °
WALL
solid;
apparent
density
≥450 kg/m³
in
Wet installation in, for example, con-
crete; masonry according to EN 1996 or
DIN 1053; solid plaster wall boards ac-
cording to EN 12859
100
next to each other: 200
EI 120 (v
e
, i↔o)
S
9
Wall: 75
Ceiling: 75
lightweight
partition
wall
Classifica-
tion accord-
ing to EN
13501-2 or
comparable
national
standards
in
Wet installation in lightweight partition
walls with metal posts and panelling on
both sides
100
next to each other: 200
EI 90 (v
e
, i↔o) S
12
Wall: 90
2)
Ceiling: 80
2)
Dry installation with additional installa-
tion frame ER-P1 in lightweight partition
walls with metal posts and panelling on
both sides
100
next to each other: 200
EI 90 (v
e
, i↔o) S
14
Wall: 100
2)
Ceiling: 100
2)
Wet installation in lightweight partition
walls with metal posts and panelling on
one side
115
next to each other: 220
2)
EI 90 (v
e
, i↔o) S
15
Wall: 110
2)
Ceiling: 100
2)
Dry installation with additional installa-
tion frame ER-P1 in lightweight partition
walls with metal posts and panelling on
one side
115
next to each other: 200
EI 90 (v
e
, i↔o) S
16
Wall: 110
2)
Ceiling: 100
2)
CEILIN
G
solid;
apparent
density
≥500 kg/m³
in
Wet installation in, for example, con-
crete; aerated concrete
125
next to each other: 200 EI 120 (h
o
, i↔o)
S
10
Wall: 75
on
1)
Wet installation with concrete base on,
for example, concrete; aerated concrete
125
next to each other: 200 EI 120 (h
o
, i↔o)
S
11
Wall: 75
Table 3: Usability
Additional note:
It may also be installed in walls or in and on ceilings of a lower fire resistance class. In this case, however, the fire resistance class of the
fire damper is reduced accordingly. The conditions listed above must be taken into account.
1)
Installation only in connection with a concrete base still to be made on site.
2)
Due to the construction or installation
.