4.3.1 Electrical Parameters - Auxiliary Contact
The parameters relating to the safety , available only for ATEX certification, is not possible to mount auxiliary contacts for IECEx
certification. For Russian Market the auxiliary contacts must be certified EAC Ex.
4.3.1.1 Switch type ZBWE
For ADVANCE-GRP[GD] 16/32A/63A
Maximum Supply Voltage: 415 V
Maximum Current: 4 A
Maximum Dissipation: 1W
Wiring by screw clamp 2x 1,5 mm ² or 1 x 2.5 mm ² with tip.
Torque: 0,8Nm à 1,2Nm max
4.3.1.2 Switch type M-053x
For ADVANCE-GRP[GD] 16/32A/63A
Electrical charateristics:
Contact block type M-0530 and M-0531
Category of utilisation
Parameter
AC 15
DC 13
Rated operating voltage Ue… up to
Rated current Ie…………… max
400 V
4 A
48 V
4 A
Rated operating voltage Ue… up to
Rated current Ie…………… max
500 V
4 A
-
Rated operating voltage Ue… up to
Rated current Ie…………… max
690 V
2 A
Conductors section
Max 2,5 mm
2
Max 2,5 mm
2
Schedule of limitations for components:
Rated service temperature range: from -40°C to +80°C.
4.3.2 ATEX Certification – Auxiliary Contact
Type
Vmax - Imax
Mode of
protection
ATEX Certificate
Ambient
Temperature
EX-TECH SOLUTION
ZBWE-....
415V – 4A
Ex db eb IIC Gb
INERIS 02 ATEX 9007U
-50°C / +75°C
CORTEM
M-053x
400V – 4A
Ex d e IIC
CESI 09 ATEX 016 U
-40°C / +80°C
4.3.3 IECEx Certification – Auxiliary Contact
Type
Vmax - Imax
Mode of
protection
IECEx Certificate
Ambient
Temperature
EX-TECH SOLUTION
ZBWE-....
415V – 4A
Ex db eb IIC Gb
IECEx INE 13.0063U
-50°C / +75°C
CORTEM
M-053x
400V – 4A
Ex d e IIC
IECEx CES 11.0031U
-40°C / +80°C