ADVANCE-GRP[GD]
MP39683
ZP90904-5
15
EN
• ГОСТ IEC 60079-1-2011,
• ГОСТ Р МЭК 60079-7-2012,
• ГОСТ IEC 60079-31-2010
• Electrical Equipment (EN 60947-1:2007 + A1:2011, EN 60947-3:2009 + A1:2012)
(IEC 60947-1:2007 + A1:2010, IEC 60947-3:2008 + A1:2012)
They are manufactured and tested in accordance with directive ATEX directive 2014/34/EU, IECEx scheme, EAC Ex certification
state-of-the-art engineering practice and ISO 9001.
2. TECHNICAL DATA
2.1 TYPE OF PROTECTIONS
• ATEX / IECEx:
Ex db eb IIC T
(1)
Gb - Ex tb IIIC T80°C Db IP66
Tamb.
(2)
- Tcable:
(3)
• EAC Ex:
1Ex d e IIC T
(1)
Gb X - Ex tb IIIC T80°C Db X IP66
Tamb.
(2)
- Tcable:
(3)
(1)
Temperature Class for Gas according to the table 1.
(2)
Ambient temperature range according to the table 1 when different from –20°C to +40°C.
(3)
Tcable: 80°C for type 504.16… when maximum ambient temperature is +60°C.
Tcable: 85°C for type 504.32… when maximum ambient temperature is +60°C.
Tcable: 90°C for type 504.63… when maximum ambient temperature is +60°C.
Tcable: 85°C for type 504.125…
2.2 CERTIFICATES
Atex Certificate:
INERIS 15 ATEX 0017 X
IECEx Certificate:
IECEx INE 15.0033 X
EAC Ex Certificate
НАНИО ЦСВЭ № TC RU C-IT.AA87.B.00870
2.3 AMBIENT TEMPERATURE RANGE
ADVANCE-
GRP[GD]
Socket Type (*)
Ambient
Temperature Range
(Ta)
Temperature
CLASS - Gas
Optional Auxiliary Contacts
Max. Surface
Temperature -
Dust
CORTEM M-053x TECHNOR ZBWE
504.16…
-50°C to +50°C
T6
--
Yes
T80°C
-50°C to +60°C
T5
--
Yes
504.32…
-50°C to +60°C
T4
--
--
-50°C to +50°C
T4
--
--
-50°C to +40°C
T5
--
Yes
-40°C to +60°C
T4
--
--
-40°C to +50°C
T4
Yes
--
-40°C to +40°C
T5
Yes
Yes
504.63…
-35°C to +60°C
T3
--
--
-35°C to +50°C
T3
--
--
-35°C to +40°C
T4
Yes
Yes
504.125…
-35°C to +40°C
T4
--
--
Table 1 - Ambient temperature range.
(*) For EAC Ex version add the “-xx.RU” suffix, to all code showed in the table.