ADVANCE-GRP[GD]
MP39683
ZP90904-5
17
EN
4. ELECTRICAL FEATURES
Switch Socket Type
16/32A
63A
CZ0513-180A
Rated Voltage
400V
500V
690V
400V
500V
690V
690V
Category
AC3
-
25A
-
-
50A
-
125A
AC22A
-
-
32A
-
-
63A
125A
AC23A
-
32A
-
-
-
63A
125A
4.1 CROSS SECTIONAL AREAS CONDUCTORS & TORQUE
SWITCH TERMINALS CONTACTS - TORQUE
Switch Socket Type
Cross Sectional Areas Conductors
Tightening Torque -
(Nm)
Minimum
Maximum
16A
4 mm²
10 mm²
0.8
32A
6 mm²
10 mm²
63A
16 mm²
25 mm²
2.5
125A
50 mm²
70 mm²
3.5
4.1.1 Earth Terminals
EARTH TERMINALS CONTACTS - TORQUE
Type
Cross Sectional Areas Conductors
Tightening Torque - (Nm)
16/32A
10/16 mm²
1.2
63A
Weidmuller Ex e terminal - type WPE35 35mm²
3.5
125A
50/70mm² - CZ0513-180A - Switch-Earth Terminal
4.2 AUXILIARY CONTACTS
In the sockets ADVANCE-GRP[GD] type 16A, 32A, and 63A can be install as optional 2 auxiliary contacts maximum, on model type
125A is not possible to install auxiliary contacts.
They are optional accessories with ATEX / IECEx / EAC Ex separate certificates. Installation and maintenance shall be done as
prescribed by manufacturer documents. Creepage and clearance distances shall comply with IEC EN 60079-7 / ГОСТ Р МЭК
60079-7-2012 at Table 1, current and maximum dissipated power shall not exceed the maximum value allowed.
4.3 HOW TO INSTALL AUXILIARY CONTACT
A
B
A
B
Insertion aux. contact “A”
Insertion aux. contact “A”
Insertion aux. contact “B”
Insertion aux. contact “B”
ADVANCE-GRP[GD] 16/32A