5.2 - Fill Flow Rate
Line 2 displays the make-up flow rate using either a Hall Effect
or a Reed switch type flowmeter. To calibrate the meter, press
the RIGHT ARROW key to enter the Fill Flowmeter Calibration
Submenu 5.2.
For industry-standard pulsing watermeters, The flowmeter is
calibrated by entering the number of gallons per pulse that the
watermeter provides to the controller.
We can also setup to accumulate flow using sub-unit pulses by
programming the controller with the manufacturer’s K-Factor.
If you have this sort of a flow sensor, please call the factory for
direction.
5.3 - Cumulative Fill
Line 3 shows the fill water cumulative flow. By pressing the
RIGHT ARROW key, the operator accesses the Fill Water
History Submenu 5.3. Three counters are available for
independent resets.
5.4 - Bleed Flow Rate
Line 4 shows the bleed water flow rate. Instructions for
calibration are the same as for fill water in paragraph 5.2.
5.5 - Cumulative Bleed
Line 5 shows cumulative fill. By pressing the RIGHT ARROW
key, the operator accesses the Fill Water History Submenu
5.5.
Submenu 5.2
Submenu 5.3
Submenu 5.4
Submenu 5.5
FILL WATER
FLOWMETER CALIBRATION
Enter number of
Gallons per pulse:
____
FILL WATER HISTORY
Total
Ga
220,000
Last Reset
06/01/04
Counter 1
Ga
90,000
Start Date
06/01/04
Counter 2
Ga
20,000
Start Date
06/07/04
BLEED WATER
FLOWMETER CALIBRATION
Enter number of
Gallons per Pulse
____
BLEED WATER HISTORY
Total
Ga
110,000
Last Reset
06/01/04
Counter 1
Ga
45,000
Start Date
06/01/04
Counter 2
Ga
10,000
Start Date
06/07/04