Web connection
The data for the device which loads and displays the web page are set here. With the programmable
panels, this is normally the internal controller. The local host IP address must therefore be set to
127.0.0.1.
5.2.1 Connection
Name of the connection
5.2.2 Start page
Name of the start page for this connection
5.2.3 Remote host IP
IP address of the connected PCD
5.2.4 Remote port
Remote port (80 default)
5.2.5 Default password
The web server password from the PG5 Device Configurator will be used
5.2.6 Remote info
Information regarding the PCD from which the web pages are displayed.
5.2.7 Search
Allows the network to scan for PCDs with web servers. The PCDs found can then be added to the
connection list.
5.2.8 Connection list
We recommend that you set up one or more connections (up to x16)
from the "List of connec-
tions".
Configure the connection or connections and select the connection that you would like to use
for your project. Each connection can be configured at any time.
Names for the connections are needed as URL jump targets in the Web Editor:
Example: The name of the connection in the list is conn2_http, and the name of the start page for the
project is Start.html