Quick Start Guide

Humidity and temperature transmitter

General features

Features of the housing

Symbols used

For your safety and in order to avoid any damage of the device, please follow the procedure described in 
this document and read carefully the notes preceded by the following symbol: 
 
The following symbol will also be used in this document, please read carefully the information notes 
indicated after this symbol: 

TH 210-R

Connections

Electrical connections as per NFC15-100 standard

This connection must be made by a formed and qualified technician. To make the connection, the transmitter must not 

be energized. Before making the connection, you must first check the power supply indicated on the transmitter board 

(see (b) in “Connections” part). The presence of a switch and a circuit breaker upstream the device is compulsory

Two 4-wire analogue 
output 0-5/10 V or 
0/4-20 mA

Stainless steel or 
polycarbonate 
probes

ABS V0 IP65 housing, 
with or without display

2 relay outputs

0-5 / 10 V 

4-20 mA

Power supply

TH 210-BXX models: 24 Vac/Vdc ±10%. TH 210-HXX models: 100-240 Vac, 50-60 Hz

Warning: risk of electric shock 

Output

2 x 4-20 mA or 2 x 0-20 mA or 2 x 0-5 V or 2 x 0-10 V (4 wires)

Common mode voltage < 30 VAC. Maximum load: 500 Ω (0/4-20 mA). Minimum load: 10 kΩ (0-5/10 V)

Relay outputs

2 changeover relays. NO: 5 A/NC: 3 A/240 Vac

Galvanic isolation

Inputs and outputs (models 100-240 Vac). 

Device fully protected by DOUBLE ISOLATION or REINFORCED ISOLATION 

Outputs (models 24 Vac/Vdc)

Consumption

TH 210-B: 6 VA/TH 210-H: 8 VA

Electrical connection

Screw terminal block for cable 2.5 mm². Executed following the good practices guidelines.

Type of sensor

Hygrometry: capacitive. Temperature: Pt100 1/3 as per IEC 60751 (2008)

Type of fluid

Air and neutral gases

PC communication

USB-Mini Din cable

Environment

Air and neutral gases

Conditions of use 
(°C/%RH/m)

From -10 to 50 °C. In non-condensing condition. From 0 to 2000 m.

Storage 
temperature

From -10 to 70 °C

Security

Protection class II. Pollution degree 2. Overvoltage CAT II

European directives

2014/30/EU EMC; 2014/35/EU Low Voltage; 2011/65/EU RoHS II; 2012/19/EU WEEE

Material

ABS V0 as per UL94

Protection

IP65

Display

75 x 40 mm, LCD 20 digits 2 lines.

Height of digits: 

Values: 10 mm; Units: 5 mm

Cable gland

For cables Ø 8 mm maximum

Weight

340 g

59

11

5

59

125

125

100

19

0

All dimensions are in millimeters.

Remote model

Ambient model

               TH210-HOX-R
Power supply: 

100-240 Vac

                          50-60 Hz 8 VA

Output: 

0/4...20 mA / 0...5/10 V

100-240 Vac

24 Vac/Vdc

              TH210-HOX-R
Power supply:

 24 Vac/Vdc ±10 %

                          50-60 Hz 6 VA

Output:

 0/4...20 mA / 0...5/10 V

Type d'alimentation (b) précisée sur l'étiquette
sur le côté du capteur

1

2

3

4

5

7

6

Sortie analogique 1

(out 1)

0-5/10 V 

– T

ension 

GND – Masse

0/4-20 mA – Courant 

Sortie analogique 2

(out 2)

0-5/10 V 

– T

ension 

GND – Masse

0/4-20 mA – Courant 

(a)

(c)

ou

Pour les modèles en
alimentation 

24 Vdc

-

+

(c)

ou

Pour les modèles en
alimentation 

24 Vac

Neutre (N)~

Phase (L)~

(c)

Pour les modèles en
alimentation 

100-240 Vac

Neutre (N)~

Phase (L)~

Relais 1 et 2

COM : commun

NC : normalement fermé

NO : normalement ouvert

Terre fonctionnelle

*Fusible uniquement présent sur les modèles 100-240 Vac.
Tout changement de fusible doit être réalisé appareil hors tension en utilisant un fusible TR5 630 mA 250 V.

               TH210-HOX-R
Power supply: 

100-240 Vac

                          50-60 Hz 8 VA

Output: 

0/4...20 mA / 0...5/10 V

100-240 Vac

24 Vac/Vdc

              TH210-HOX-R
Power supply:

 24 Vac/Vdc ±10 %

                          50-60 Hz 6 VA

Output:

 0/4...20 mA / 0...5/10 V

Power supply type (b) specified on the label
on the side of the transmitter

1

2

3

4

5

7

6

Analogue output 1

(out 1)

0-5/10 V 

– V

oltage

GND – Ground

0/4-20 mA – Current 

Analogue output 2

(out 2)

0-5/10 V 

– V

oltage 

GND – Ground 

0/4-20 mA – Current

(a)

(c)

or

For 

24 Vdc

 power

supply models

-

+

(c)

or

For 

24 Vac

 power

supply models

Neutral (N)~
Phase (L)~

(c)

For 

100-240 Vac

 power

supply models

Neutral (N)~
Phase (L)~

Relays 1 and 2

COM: common

NC: normally closed

NO: normally opened

Operational grounding

*Fuse present only for 100-240 Vac models.
  Every fuse replacement must be performed with a power off device using a TR5 630 mA 250 V fuse.

               TH210-HXXX-R
Alimentación: 

100-240 VAC

                       50-60 Hz, 8 VA

Salidas: 

0/4...20 mA / 0...5/10 V

100-240 Vac

24 Vac/Vdc

               TH210-BXXX-R
Alimentación: 

24 VAC/VDC ±10 %

                          50-60 Hz 6 VA

Salida: 

0/4...20 mA / 0...5/10 V

Tipo de alimentación (b) especificada en la
etiqueta lateral del transmisor

1

2

3

4

5

7

6

Salida analógica 1

(Out 1)

0-5/10 V 

– V

oltaje

GND 

– T

ierra

0/4-20 mA – Corriente 

Salida analógica 2

(Out 2)

(a)

(c)

o

Alimentación a 
24 Vdc

-

+

(c)

o

Alimentación a 
24 Vac

Neutro (N)~
Fase (L)~

(c)

Alimentación 
100-240 Vac 

Neutro (N)~
Fase (L)~

Relés 1 y 2

COM: común

NC: normalmente cerrado

NO: Normalmente abierto

Toma a tierra

*Fusible solo en modelos con alimentación 100-240 Vac
El remplazo del fusible debe ser efectuado con el dispositivo con la alimentación desconectada usando un fusible TR5 630 mA 250 V .

0-5/10 V 

– V

oltaje

GND 

– T

ierra

0/4-20 mA – Corriente 

1.  DIP switch (d)
2.  LCC-S software connection
3.  Relays
4.  Analogue outputs (a)
5.  F3.20* fuse
6.  Power supply terminal block (c)
7.  Cable glands

-

+

Alimentation

24 Vdc

N-

L+

N

L

Alimentation 24 Vac

classe II norme EN61558-2-6

N-

L+

Pe

N

L

ou

N

L

Alimentation

N-

L+

Pe

N

L

230 Vac

230 Vac

N

L

Alimentation

100-240 Vac

N-

L+

-

+

0-5/10 V

0/4-20 mA

Afficheur régulateur ou

automate 

type passif

A

-

+

0-5/10 V

0/4-20 mA

Afficheur régulateur ou

automate 

type passif

V

Sortie 4-20 mA

Sortie 0-10 V

-

+

24 Vdc

Power supply

N-

L+

N

L

24 Vac power supply

class II EN61558-2-6 standard

N-

L+

Pe

N

L

or

N

L

Power supply

N-

L+

Pe

N

L

230 Vac

230 Vac

N

L

100-240 Vac

Power supply

N-

L+

-

+

0-5/10 V

0/4-20 mA

Regulator display or

PLC/BMS 

passive type

A

-

+

0-5/10 V

0/4-20 mA

Regulator display or

PLC/BMS 

passive type

V

4-20 mA output

0-10 V output

-

+

Fuente

24 Vdc 

N-

L+

N

L

Fuente de alimentación 24 Vac

clase II norma EN61558-2-6

N-

L+

Pe

N

L

o

N

L

Fuente de alim.

N-

L+

Pe

N

L

230 Vac

230 Vac

N

L

Fuente

100-240 Vac

N-

L+

-

+

0-5/10 V

0/4-20 mA

PLC/BMS de tipo pasivo

Regulador/display o

PLC/BMS de 

tipo pasivo

A

-

+

0-5/10 V

0/4-20 mA

Regulador/display o

PLC/BMS de 

tipo pasivo

V

Salida 4-20 mA

Salida 0-10 V

On 100-240 Vac models, if a fuse protection is used for the power line, it is imperative to use delayed-action 
fuses in order to absorb the surge of current when first turned on the transmitter.

The selection of the output signal in voltage (0-10 V or 0-5 V) or in current 
(4-20 mA or 0-20 mA) is made via the DIP switch (d) of the electronic board 
of the transmitter: put the on-of switches as shown in the table below:

Configurations

4-20 mA

0-10 V

0-5 V

0-20 mA

Combinations

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

1   2   3   4

• 

Connection of the output in current 
4-20 mA: 

• 

Connection of output in voltage 
0-10 V: 

• 

For transmitters with 24 Vdc power supply: 

• 

For transmitters with 24 Vac power supply: 

• 

For transmitters with 100-240 Vac power supply:

-

+

Alimentation

24 Vdc

N-

L+

N

L

Alimentation 24 Vac

classe II norme EN61558-2-6

N-

L+

Pe

N

L

ou

N

L

Alimentation

N-

L+

Pe

N

L

230 Vac

230 Vac

N

L

Alimentation

100-240 Vac

N-

L+

-

+

0-5/10 V

0/4-20 mA

Afficheur régulateur ou

automate 

type passif

A

-

+

0-5/10 V

0/4-20 mA

Afficheur régulateur ou

automate 

type passif

V

Sortie 4-20 mA

Sortie 0-10 V

-

+

24 Vdc

Power supply

N-

L+

N

L

24 Vac power supply

class II EN61558-2-6 standard

N-

L+

Pe

N

L

or

N

L

Power supply

N-

L+

Pe

N

L

230 Vac

230 Vac

N

L

100-240 Vac

Power supply

N-

L+

-

+

0-5/10 V

0/4-20 mA

Regulator display or

PLC/BMS 

passive type

A

-

+

0-5/10 V

0/4-20 mA

Regulator display or

PLC/BMS 

passive type

V

4-20 mA output

0-10 V output

-

+

Fuente

24 Vdc 

N-

L+

N

L

Fuente de alimentación 24 Vac

clase II norma EN61558-2-6

N-

L+

Pe

N

L

o

N

L

Fuente de alim.

N-

L+

Pe

N

L

230 Vac

230 Vac

N

L

Fuente

100-240 Vac

N-

L+

-

+

0-5/10 V

0/4-20 mA

PLC/BMS de tipo pasivo

Regulador/display o

PLC/BMS de 

tipo pasivo

A

-

+

0-5/10 V

0/4-20 mA

Regulador/display o

PLC/BMS de 

tipo pasivo

V

Salida 4-20 mA

Salida 0-10 V

-

+

Alimentation

24 Vdc

N-

L+

N

L

Alimentation 24 Vac

classe II norme EN61558-2-6

N-

L+

Pe

N

L

ou

N

L

Alimentation

N-

L+

Pe

N

L

230 Vac

230 Vac

N

L

Alimentation

100-240 Vac

N-

L+

-

+

0-5/10 V

0/4-20 mA

Afficheur régulateur ou

automate 

type passif

A

-

+

0-5/10 V

0/4-20 mA

Afficheur régulateur ou

automate 

type passif

V

Sortie 4-20 mA

Sortie 0-10 V

-

+

24 Vdc

Power supply

N-

L+

N

L

24 Vac power supply

class II EN61558-2-6 standard

N-

L+

Pe

N

L

or

N

L

Power supply

N-

L+

Pe

N

L

230 Vac

230 Vac

N

L

100-240 Vac

Power supply

N-

L+

-

+

0-5/10 V

0/4-20 mA

Regulator display or

PLC/BMS 

passive type

A

-

+

0-5/10 V

0/4-20 mA

Regulator display or

PLC/BMS 

passive type

V

4-20 mA output

0-10 V output

-

+

Fuente

24 Vdc 

N-

L+

N

L

Fuente de alimentación 24 Vac

clase II norma EN61558-2-6

N-

L+

Pe

N

L

o

N

L

Fuente de alim.

N-

L+

Pe

N

L

230 Vac

230 Vac

N

L

Fuente

100-240 Vac

N-

L+

-

+

0-5/10 V

0/4-20 mA

PLC/BMS de tipo pasivo

Regulador/display o

PLC/BMS de 

tipo pasivo

A

-

+

0-5/10 V

0/4-20 mA

Regulador/display o

PLC/BMS de 

tipo pasivo

V

Salida 4-20 mA

Salida 0-10 V

Summary of Contents for TH 210-R

Page 1: ...TH 210 R Quick Start Guide www sauermanngroup com EN FR ES ...

Page 2: ...eplacement must be performed with a power off device using a TR5 630 mA 250 V fuse TH210 HXXX R Alimentación 100 240 VAC 50 60 Hz 8 VA Salidas 0 4 20 mA 0 5 10 V 100 240 Vac 24 Vac Vdc TH210 BXXX R Alimentación 24 VAC VDC 10 50 60 Hz 6 VA Salida 0 4 20 mA 0 5 10 V Tipo de alimentación b especificada en la etiqueta lateral del transmisor 1 2 3 4 5 7 6 Salida analógica 1 Out 1 0 5 10 V Voltaje GND T...

Page 3: ...beside Rotate the housing in clockwise direction until you hear a click which confirms that the transmitter is correctly installed 2 Mounting Capteur transmetteur d hygrométrie et de température Caractéristiques générales Caractéristiques du boîtier TH 210 R Sortie analogique 4 fils 0 5 10 V ou 0 4 20 mA Sondes en inox ou en polycarbonate Boîtier ABS V0 IP65 avec ou sans afficheur 2 sorties relais...

Page 4: ...fin d absorber le pic de courant à la mise sous tension du capteur La sélection du signal de sortie en tension 0 10V ou 0 5V ou en courant 4 20 mA ou 0 20 mA se fait avec le switch d de la carte électronique du capteur en disposant les interrupteurs de la manière suivante Configurations 4 20 mA 0 10 V 0 5 V 0 20 mA Combinaisons 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 ...

Page 5: ... la alimentación desconectada usando un fusible TR5 630 mA 250 V 0 5 10 V Voltaje GND Tierra 0 4 20 mA Corriente 1 DIP switch d 2 Conector para LCC S 3 Relés 4 Salidas analógicas a 5 Fusible F3 20 6 Bloque de alimentación c 7 Prensa estopas Alimentation 24 Vdc N L N L Alimentation 24 Vac classe II norme EN61558 2 6 N L Pe N L ou N L Alimentation N L Pe N L 230 Vac 230 Vac N L Alimentation 100 240 ...

Page 6: ...lógicas configurables Los transmisores TH 210 R disponen de dos salidas analógicas que corresponden a los parámetros mostrados Puede activar una o las dos salidas y seleccionar entre humedad temperatura y parámetros calculados La configuración por defecto es humedad relativa en el canal 1 0 100 HR y temperatura en el canal 2 0 50 C Puede configurar rangos de medición con cero central p ej 40 0 50 ...

Page 7: ...tail service clients Portal de servicio al cliente Portale servizio clienti Use our Customer service portal to contact us Utilisez notre Portail service clients pour nous contacter Contacte con nosotros a través del Portal de servicio al cliente Utilizzate il nostro Portale servizio clienti per contattarci Download the full manual Télécharger le manuel complet Descargue el manual de usuario Scaric...

Reviews: