KDB-GOM
Series
- 41 -
4. Installation of the flue
4.1 PVC Venting Method
■
The KDB-GOM Series boiler may be vented using 75mm schedule-40 venting materials.
■
Cut all lengths of pipe cleanly maintaining a 90-degree square edge. Use long radius elbows whenever possible.
■
Use only the type of adhesive recommended by the stainless pipe manufacturer.
■
Keep an uphill slant from boiler to the outside to ensure that all condensed water inside the pipe will return back to
the boiler.
■
Do not place the outdoor termination kit in an area where discharge gasses will be directed towards evergreen
shrubbery.
■
Assemble the flue using the following illustration as a guide. Your installation may vary slightly from the illustration
shown below.
Use the optional Vent Termination Kit for venting the KDB-GOM boiler to outside area.
Use the optional Vent Termination Kit for venting the KDB-GOM boiler to outside area.
Use the optional Vent Termination Kit for venting the KDB-GOM boiler to outside area.
Use the optional Vent Termination Kit for venting the KDB-GOM boiler to outside area.
- Standard : The Stainless Steel Concentric Flue Kit for KDB-GOM models.
“A” : 75
㎜×
㎜×
㎜×
㎜×
1.0m LENGTH STAINLESS FLUE PIPE
“B” : 75
㎜×
㎜×
㎜×
㎜×
0.5m LENGTH STAINLESS FLUE PIPE
“C” : 75
㎜×
㎜×
㎜×
㎜×
90-DEG. STAINLESS ELBOW
Shown : 75
㎜
㎜
㎜
㎜
(3
″
″
″
″
) Stainless Venting.
“C”
“A” or “B”
(Maximum Allowable
Flue Length = 5 m)
Min. 250
㎜
(10
″
)
Vent Termination Kit
Exhaust
Intake Air
Min. 600
㎜
(2 ft) from ground
(
Note!
- Install the vent termination kit in an
area away from plants,
people and
animals)
φ
75
㎜
(3
″
″
″
″
)
Type 304
stainless steel
only
NOTE
ⅰ
) Intake Air :
φ
75
㎜
(3
″
″
″
″
) stainless steel.
ⅱ
) Exhaust :
φ
75
㎜
(3
″
″
″
″
) Stainless steel.
ⅲ
) Maximum three 90
°
elbows.
ⅳ
) Slant flue pipe 2-3
°
away from boiler to outside,
to drain condensate.
Ground
KDB-GOM
BOILER
“C”
To Drain
Install Horizontal Drip
Tee
If Required