SATEL ACU-280
23
Temp. corr.
– you can correct the temperature information sent by the device by up to
±3.5°C.
ECO
– if this option is enabled, periodical communication with the device takes place every
3 minutes. Thus the battery life can be extended up to four times.
Remember that with the “ECO” option enabled for:
detectors – delay between arming / disarming and changing the detector operating
mode (active / passive) can be up to three minutes,
ASP-215 siren – delay in starting / stopping the signaling can be up to three minutes.
7.3.1 Configuring devices using the DLOADX program
Before making any changes, click on the “Read” button, and after making the changes – on
the “Write” button. The data on wireless devices are not read / written when you use buttons
in the DLOADX main menu.
ARU
In the “ARU” column:
leave the field blank, if the device is to communicate directly to the controller,
enter the ARU-200 repeater number in the list of wireless devices, if the device is to
communicate to the controller via the repeater (the repeater takes up two positions on the
list of devices – enter the number of the first of them).
Configuration
In the “Configuration” column you can configure additional parameters and options for the
ABAX 2 devices.
ADD-200
Dusk sensor – enter a number from the 1 to 16 range to determine sensitivity (1 – minimum;
16 – maximum).
Temperature sensor – enter in turn:
letter H (high temperature threshold) or L (low temperature threshold),
number from a range of -30 to +70 (with 0.5 accuracy) to define temperature,
number from a range of 0.5 to 10 (with 0.5 accuracy) to define tolerance.
AGD-100 (AGD-200)
Enter a digit from the 1 to 3 range to set the sensitivity (1 – low , 2 – medium, 3 - high).
AMD-100 (AMD-200) / AMD-101 (AMD-201)
Do not configure.
AMD-102 (AMD-202)
Magnetic contact – do not configure.
Roller shutter input – enter 2 digits:
1st digit – number of pulses: from 1 to 8.
2nd digit – pulse validity: 0 (30 seconds), 1 (120 seconds), 2 (240 seconds) or 3 (unlimited
duration).
AOCD-250 (AOCD-260)
Enter 2 digits:
1st digit – sensitivity of PIR sensor: from 1 to 4 (1 – minimum; 4 – maximum).
2nd digit – sensitivity of microwave sensor: from 1 to 8 (1 – minimum; 8 – maximum).