Chapter 5 Configuring the EM720
Configuring Billing/TOU
96
EM720 Power Quality and Revenue Meter
The daily profile setup allows you to specify the daily tariff
change points with a 15-minute resolution for 4 seasons
using 4 different daily schedules for each season.
To configure your daily profiles:
1. Select the desired season and day type.
2. Select the start time for each tariff change point and
the corresponding active tariff number.
3. Repeat the setup for all active profiles.
The first tariff change point is fixed at 00:00 hours, and the
last tariff change you specified will be in use until 00:00
hours on the next day.
NOTE
The billing monthly and daily profile files, and your billing
data display are automatically configured for the number of
active tariffs you defined in the meter TOU daily profile.
Configuring the Season Tariff and DST Schedule
The EM720 TOU calendar provides a season tariff schedule
and an option for scheduled daylight savings switch dates.
To configure your season tariff schedule, select Energy/TOU
from the Meter Setup menu, and then click on the TOU
Calendar tab.
The meter TOU calendar allows you to configure any tariff
schedule based on any possible utility regulation. The
calendar provides 48 entries that allow you to specify profiles
for working days and holidays through all seasons in any